INSTallaTION
Specification
42
| WPE-I H(K) 230 Premium
www.stiebel-eltron.com
16.4 Data table
WPE-I H 230 Premium
Output details apply to new appliances with clean heat exchangers.
The power consumption figures for the integral auxiliary drives are maximum values and may vary subject to operating point.
The power consumption of the integral auxiliary drives is included in the output details of the heat pump (to EN 14511).
WPE-I 04 H 230
Premium
WPE-I 06 H 230
Premium
WPE-I 08 H 230
Premium
WPE-I 12 H 230
Premium
WPE-I 15 H 230
Premium
202613
238610
238611
238612
238613
Heating output
Heating output at B0/W35 (min./max.)
kW
1.04 - 4.19
1.04 - 6.57
1.04 - 7.64
2.14 - 12.66
2.14 - 14.78
Heating output at B0/W35 (EN 14511)
kW
1.96
2.37
2.78
4.19
5.18
Heating output at B0/W55 (EN 14511)
kW
1.28
2.01
2.42
4.2
4.72
Power consumption
Power consumption at B0/W35 (EN 14511)
kW
0.43
0.52
0.6
0.84
1.07
Power consumption at B0/W55 (EN 14511)
kW
0.47
0.69
0.79
1.34
1.48
Power consumption, emergency/booster heater
kW
5.8
5.8
5.8
5.8
5.8
Max. power consumption, circulation pump on the
heating side
W
45
45
45
76
76
Max. power consumption, circulation pump on the
source side
W
140
140
140
140
140
Coefficients of performance
SCOP (EN 14825)
5.07
5.20
5.12
5.59
5.44
Coefficient of performance at B0/W35 (EN 14511)
4.60
4.60
4.67
5.01
4.86
Coefficient of performance at B0/W55 (EN 14511)
2.73
2.91
3.07
3.13
3.18
Sound emissions
Sound power level (EN 12102)
dB(A)
38 - 40
38 - 43
39 - 45
39 - 46
39 - 47
Application limits
Max. permissible pressure
MPa
0.3
0.3
0.3
0.3
0.3
Min. application limit on the heating side
°C
15
15
15
15
15
Max. application limit on the heating side
°C
75
75
75
75
75
Min. application limit, heat source
°C
-5
-5
-5
-5
-5
Max. application limit, heat source
°C
20
20
20
20
20
Shutdown pressure, brine pressure switch (positive
pressure)
MPa
0.7
0.7
0.7
0.7
0.7
Energy data
Energy efficiency class
A+++/A+++
A+++/A+++
A+++/A+++
A+++/A+++
A+++/A+++
Electrical data
Starting current (with/without starting current limiter)
A
<25
<25
<25
<25
<25
Emergency/booster heater fuse protection
A
2 x B 16
2 x B 16
2 x B 16
2 x B 16
2 x B 16
Control unit fuse protection
A
1 x B 16
1 x B 16
1 x B 16
1 x B 16
1 x B 16
Compressor fuse protection
A
1 x B 16
1 x B 16
1 x B 16
1 x B 25
1 x B 25
Rated voltage, emergency/booster heater
V
230
230
230
230
230
Rated voltage, control unit
V
230
230
230
230
230
Rated voltage, compressor
V
230
230
230
230
230
Frequency
Hz
50
50
50
50
50
Emergency/booster heater phases
2/N/PE
2/N/PE
2/N/PE
2/N/PE
2/N/PE
Control unit phases
1/N/PE
1/N/PE
1/N/PE
1/N/PE
1/N/PE
Compressor phases
1/N/PE
1/N/PE
1/N/PE
1/N/PE
1/N/PE
Max. operating current
A
8.4
13
15.09
24.32
24.48
Versions
Refrigerant
R454C
R454C
R454C
R454C
R454C
Refrigerant charge
kg
2.2
2.2
2.2
3.1
3.1
Global warming potential of the refrigerant (GWP100)
148
148
148
148
148
CO
2
equivalent (CO
2
e)
t
0.32
0.32
0.32
0.45
0.45
Condenser material
1.4401/Cu
1.4401/Cu
1.4401/Cu
1.4401/Cu
1.4401/Cu
Evaporator material
1.4401/Cu
1.4401/Cu
1.4401/Cu
1.4401/Cu
1.4401/Cu
Circulation pump type on the heating side
Yonos PARA 25/7.0 Yonos PARA 25/7.0 Yonos PARA 25/7.0 Yonos PARA 25/7.5 Yonos PARA 25/7.5
Circulation pump type, source side
Grundfos UPML
Grundfos UPML
Grundfos UPML
Grundfos UPML
Grundfos UPML
IP rating
IP20
IP20
IP20
IP20
IP20
Summary of Contents for WPE-I 04 H 230 Premium