background image

 

 

 

 

 

 

Installation and Operation Instructions 

 

 

 
 

NOTE: Read this entire instruction sheet before starting the installation.

  

     

        

I

MPORTANT 

C

ONSIDERATIONS

 

Improper  installation,  adjustment,  alteration,  service, 
maintenance,  or  use  can  cause  fire,  electrical  shock,  or 
other  conditions  which  may  cause  personal  injury  or 
property  damage.  Consult  your  supplier  or  Steril-Aire  for 
information or assistance. 

 

Understand  the  signal  words 

DANGER

WARNING

,  a n d  

CAUTION

.  These  words  are  universally  used  for  overall 

safety. 

DANGER 

identifies the most serious hazards which 

will  result  in  severe  personal  injury  or  death. 

WARNING 

signifies  hazards  which  could  result  in  personal  injury  or 
death. 

CAUTION 

is  used  to  identify  unsafe  practices 

resulting  in  minor  personal  injury  or  product  and  property 
damage. 

 
 

WARNING: 

Before  performing  maintenance  or  service  on  fixture, 
ensure  unit  is  unplugged.  Electrical  shock  can  cause 
injury or death. 

 

 

CAUTIONS:

 

• 

Never  expose  eyes  or  skin  to  UVC  light.  Wear  gloves, 
face  shield/glasses  (per  ANSI  Z87.1)  and  cover  all 
exposed skin. 

 

• 

Do  not  touch  UVC  Emitter

®

  germicidal  lamp  without 

gloves.  Damage  to  Emitter  may  result.  Oil  from 
fingerprints  will  permanently  etch  glass  of  Emitter  and 

weaken  structure. If  necessary, clean  Emitter using  a 
Steril-Aire cleaning kit, isopropyl alcohol and a lint-free 
wipe may be substituted. 

• 

UVC  Emitters  are  fragile.  To  prevent  accidental 
breakage handle the UVC Emitter with care. 

• 

Voltages  outside  of  the  range  designed  for the unit 
will  void  the  warranty  and  do  permanent damage to 
the entire unit. 

• 

Emitter contains a small quantity of mercury. 
If  an  Emitter  breaks,  clean  and  dispose  of  with  the 
same care as a fluorescent lamp. 

• 

UVC  energy  may  cause  damage  to  non-metallic 
components.  Such  components  shall  be  protected 
with  UV  resistant  material  such  as  aluminum  foil, 
aluminum duct tape, metallic shields, etc. 

• 

The  qualified  installer  or  agency  must  use factory 
kits and accessories when installing this product. 

 

For your safety ensure that the Kit is electrically 
connected to a proper power source, on/off switch, 
interlock switch (or control panel) and fuse. 

 

Upon  completing  the  installation,  the  UVC  Emitters 
should  be  operated  continuously,  24/7,  to  preclude 
the development of mold and bacteria.  
 
Dispose  of  used  Emitters  in  accordance  with  local 
regulations  regarding  the  disposal  of  fluorescent 
lamps.

Enhanced UVC Kit  

      Part Number: 10000180-1 

 
Patents 5,817,276/ 6,245,293/ 6,267,924/ 6,280,686/ 6,313,470/ 6,423,882/ 6,500,267 
/6,589,476/ 6,627,000/ 6,783,578/

 

7,140,749/ 7,282,728/ 7,459,694  & others pending 

 

                                                      

Made in the USA

 

 

 

Summary of Contents for Enhanced UVC Kit

Page 1: ... Emitter and weaken structure If necessary clean Emitter using a Steril Aire cleaning kit isopropyl alcohol and a lint free wipe may be substituted UVC Emitters are fragile To prevent accidental breakage handle the UVC Emitter with care Voltages outside of the range designed for the unit will void the warranty and do permanent damage to the entire unit Emitter contains a small quantity of mercury ...

Page 2: ...d Electrical shock can cause injury or death 1 The Emitter access door or panel should be interlocked interlock switch P N 90000120 with the power source to turn Emitter s off when the Air Handler is opened It should have signs provided alerting maintenance personnel to the possible hazard of looking at or exposing skin to UVC energy Service accesses may be equipped with a glass or Lexan window to...

Page 3: ...ut Emitters should be replaced after 9000 hours of use 1 year TROUBLESHOOTING Symptom Possible Causes Corrective Action Emitter does not light Momentary loss of power Reset Power Turn off power for 10 Seconds and then turn power on Poor connection Check connection to Emitter Check wiring connections Reset Power Incorrect wiring Inspect circuit to wiring diagram Dirty pins Clean pins Reset Power Sy...

Page 4: ...ingle Ended Emitter 21000510 EGTS 36 VO Enhanced 36 Single Ended Emitter 21000610 EGTS 42 VO Enhanced 42 Single Ended Emitter 21000910 EGTS 50 VO Enhanced 50 Single Ended Emitter 21000810 EGTS 61 VO Enhanced 61 Single Ended Emitter Replacement Parts Part Number Description 10000180 Power Supply Replacement for UVC Kit RIK 90000812 Spring Clips Kit 50000130 03 Enhanced Emitter Connection Cable 3 ft...