Fire Control Panel FS4000
♦
2 lines
120h
32h
♦
4 lines
98h
24h
♦
6 lines
80h
20h
♦
8 lines
68h
16h
4.7.3. Consumption on backup batteries supply:
−
Configuration of 2 lines
- < 35mA at 24V
−
Configuration of 4 lines
- < 45mA at 24V
−
Configuration of 6 lines
- < 55mA at 24V
−
Configuration of 8 lines
- < 65mA at 24V
4.8.
Power supply to external devices:
−
voltage
- (19÷24)V
−
maximum current value (including current
of controllable outputs)
- 1,2
А
4.9.
Fuses:
−
Main supply 230V
- 4.0A
−
Backup battery
- 6,0
А
−
Power supply to external devices
-1, 85
А
automatic
−
Controllable outputs
- 1,1
А
automatic
4.10. Dimensions
- 313
х
218
х
85mm
4.11. Weight, backup batteries not included
- 1,5kg
5. Contents of delivery:
−
Fire control panel FS4000
- 1 pc
−
End of line module “EOL”
♦
for 2 lines
- 2 pcs
♦
for 4 lines
- 4 pcs
♦
for 6 lines
- 6 pcs
♦
for 8 lines
- 8 pcs
−
Resistor 5,6k
Ω
/ 0,25W
- 2 pcs
−
Fuse 6,0A
- 1 pc
−
Fuse 4,0A
- 1 pc
−
Cable bridge
- 1 p
с
−
Keyswitch for Access level 2
- 2 pcs
−
CD with Instruction manual and Instruction for the authorized staff - 1 pc
−
Packing
- 1 pc
6. General information
6.1. Access levels
There are 4 levels of access to the variable indications and control functions of FS4000
6.1.1. Access level 1
All persons who would presumably find out and react to alarm for fault condition or fire condition
have access to level 1. All light indicators are visible here.
6.1.2. Access level 2
For the personnel in charge for the fire protection; they shall be trained and authorized to operate the
fire control panel in the following conditions:
Instruction manual
Page 7
Revision 4/02.11