Fire Control Panel FS4000
- right indicator
(if no other lines are set to test condition).
12. Delay of outputs
12.1. Description
The Fire control Panel registers the time delayof the outputs after manual operation for setting
the appropriate value.The time delay is set by a combination of 1
st
2
nd
and 3
rd
discharge of DIP switch
(pos.3, Figure 1) (Table 4) and can be 0, 1, 2, 3, 4, 5, 6 or 7 minutes. At time delay set to ''0'' – the
outputs are activated immediately after the Fire control panel enters Fire condition.
Time delay setting is performed by moving the first three discharges of microswitchers (pos 3,
fig .1) in the following tables :
Table 5
DIP
0
minutes
1
minute
2
minutes
3
minutes
4
minutes
5
minutes
6
minutes
7
minutes
1 OFF OFF OFF OFF ON ON ON ON
2 OFF OFF ON ON OFF OFF ON ON
3 OFF ON OFF ON OFF ON OFF ON
When the time delay is set to
≠
0, the indicator is illuminated with continuous yellow light
13. User configuration of the outputs
The Fire Controll Panel provides the option for inserting combinations for outputs activation .8
constant combinations are set. An operating combination shall be chosen by 6
th
, 7
th
, and 8
th
discharge
DIP switch (pos.3, fig.1).
Possible combinations are given in Table 6.
Table 6
Rel 1
Rel 2
Out 1
Out 2
1
DIP
position
6
OFF
7
OFF
8
OFF
Switches On
immediately
Switches On
with time delay
Switches On
with time
delay
Switches On
with time
delay
2
DIP
position
6
OFF
7
OFF
8
ON
Switches On
immediately
Switches On
immediately
Switches On
with time
delay
Switches On
with time
delay
3
DIP
position
6
OFF
7
ON
8
OFF
Switches On
with time delay
Switches On
with time delay
Switches On
with time
delay
Switches On
with time
delay
4
DIP
position
6
OFF
7
ON
8
ON
Switches On
with time delay
Switches On
with time delay
Switches On
immediately
Switches On
immediately
5
DIP
position
6
ON
7
OFF
8
OFF
Switches On
only in Fire
condition of line
1
Switches On
only in Fire
condition of
line 2
Switches On
with time
delay
Switches On
with time
delay
Instruction manual
Page 18
Revision 4/02.11
of 24