Fire Control Panel FS4000
Fire control panel FS4000 monitors the fire alarm lines by consecutively scanning their condition.
Depending on the current value, the line can be in normal condition, in fire condition or in a fault
condition (short circuit or break). Simultaneously, a constant control for removed fire detectors is
being carried out, provided that the fire alarm installation is designed and completed as shown on the
diagram of section 13.3. Control over the controllable outputs of fault condition (short circuit or break)
is being carried out as well.
The fire control panel FS4000 operates in five basic modes: Duty Mode, Fire Condition, Fault
Condition, Disabled Component Mode and Test Mode.
7. Duty mode
7.1. Description
The fire control panel is in Duty Mode, when it is not in Fire condition or in Fault condition.
7.2. LED and sound indication
In Duty mode are active only the green LED indicator
(Power supply) and the yellow
indicator
if a short circuit is set for the outputs. The local sounder is off.
7.3. Using the buttons
Active buttons in Duty mode:
-
pressing the button tests the LED indication and sound signaling;
-
using the button in this mode activates the controllable outputs (or suppresses them if
they were activated ). The aim is to signal for forced evacuation if necessary.
7.4. Additional option
In FS4000 there is opportunity for configuring line(s) in a definite way so that if signal for Fire
condition, the Fire Control Panel enters directly in Fire condition 2
nd
stage. Configuring is described in
Table 10.2 and it is in accordance with Table 3. Setting a line in this mode is performed by manual
operation of placing a pair of switchers in appropriate line positions (ON ON).