NBC DC 12V 1B  

       

(DC/DC Battery Charger) 

 

Introduction 

NBCDC 12V 1B is the complete solution to use only one product for control and recharging a 12V 7,2 Ah 
acid lead battery, for the management of a maximum load of 3A. 
The Control Unit uses a DC supply voltage (Vin 12-32 Vdc) and is optimized for use in combination with 
photovoltaic panels. 
 

Functionality 

NBCDC 12V 1B is able to recharge a 12V battery with a maximum DC supply voltage load of 3A. The Battery Charger have a STEP-DOWN 
architecture and the charging voltage is compensated by temperature with an external NTC sensor (optional). 
Inside the Control Unit there is also a control loop for the optimization of the charge of the battery depending of the solar irradiation (MPPT). 

Battery status monitoring during normal function (in presence of DC supply voltage): 

DC Supply Voltage LED indicator lights GREEN, DC Supply Voltage alarm NOT ACTIVE.

 

 - Battery disconnected or short circuit (Battery LED lit with RED color, alarm output ACTIVATED) 
 - Battery connected and charged, voltage higher than 13V (Battery LED lit with GREEN color, alarm output NOT ACTIVATED) 
 - Battery connected and in charging, voltage in the range 11.5V - 13V and charging current higher than 50 mA, battery is charging (Battery LED 
blinking RED and GREEN, alarm output NOT ACTIVATED) 

 

- Battery connected with voltage lower than 11.5V, battery is considered not compliant with the required specifications “battery damaged” (Battery 

LED lit with RED color, alarm output ACTIVATED) 

Battery status monitoring during emergency condition (lack of DC voltage power supply): 

DC Supply Voltage LED indicator lights RED, DC Supply Voltage alarm ACTIVE. 
In an emergency status, so when the battery starts running, the device allows you to monitor the battery voltage. When the battery voltage drops 
below 9.5V the device will give an alarm (RED LED ON and alarm output ACTIVE). 
 

General Technical Data 

DATI TECNICI GENERALI

Input voltage 

 

 

14-30 Vdc,  

Battery charging voltage (no load) 

14.5 V 

Charging current  

1 A Max 

Battery type 

12V – 7,2 Ah  acid lead 

Connection cables sections 

Battery cables: min 0.75 mm

2

 / Alarm cables: min 0,35  mm

2

 

Housing dimensions 

Box: IP 20, Thickness: 17 mm, Height: 90 mm, Width: 60 mm 

Battery full charging time 

24 h 

Working temperature 

0° 

 50°C 

Storage temperature 

-10° 

 +70°C 

Battery Status 

The control unit is able to detect certain conditions that allow an analisys of the status of the battery: 

Battery status during normal function (in presence of DC supply voltage) 

Battery status 

LED 

(Vin_S) 

LED 

(Bat_S) 

Battery output state 

alarm    ( Bat_F) 

Battery supply voltage 

alarm    (Vin_F) 

Battery disconnected, short circuit or 
discharge 

Green ON 

Red ON 

Active (CLOSED) 

Not active (OPEN) 

Battery connected and charged 
(voltage higher than 13V) 

Green ON 

Green ON 

Not active (OPEN) 

Not active (OPEN) 

Battery connected in charge (battery voltage 
in the range 11.5V - 13V) 

Green ON 

Blinking 

RED / GREEN 

Not active (OPEN) 

Not active (OPEN) 

 

Battery status during emergency condition (lack of DC supply voltage) 

Stato della batteria 

LED 

(Vin_S) 

LED 

(Bat_S) 

Battery output state 

alarm    ( Bat_F) 

Battery supply voltage 

alarm    (Vin_F) 

Battery worn out 
(voltage lower than 9.5V) 

Red ON 

Red ON 

Active (CLOSED) 

Active (CLOSED) 

Battery connected and charged 
(voltage higher than 9.5V) 

Red ON 

Green ON 

Not active (OPEN) 

Active (CLOSED) 

 

 
 