13
A.
Dial-up 1: Limit mode optional
OFF: NC mode(Factory setting)
ON : NO mode
Limit switch direction setting(J1):
Normal :Short circuit cap simultaneously No1 and No2 of J1 (Factory setting)
If motor system install at left of gate . Please adjust the J1 ,short the cap simultaneously No2 and No3
B. Dial-up 2: Infrared mode
OFF: NC mode(Factory setting)
ON: NO mode
If the gate meet obstacles during closing, It will auto stop and auto open. After The gate complete open to its
place, it will auto close again if the obstacle disappear within 2s, if not , it will not auto close until to the
obstacle disappear
C. Dial-up 3 &4: Auto close time setting
Auto close function activated after gate complete open to its place and stop by limit switch
Dial-up 3 &4, OFF-OFF: Auto close function disabled(Factory setting)
Dial-up 3 &4, ON-OFF: 10S
Dial-up 3 &4, ON-ON: 30S
Dial-up 3 &4, OFF-ON: 60S
D. Dial-up 5&6: Auto close time setting when pedestrian mode activated
When remote control triggers the pedestrian mode (remote control button 2 or 4), the gate will stop after
open 6s. If auto close function activated, the gate will auto close after gate open to 6s. Auto close time
setting as follows
:
Dial-up 5 &6, OFF-OFF: Auto close function disabled(Factory setting)
Dial-up 5 &6, ON-OFF: 5S
Dial-up 5 &6 , ON-ON: 10S