IMPORTANT -  CE  &  SAFETY REQUIREMENTS 

This product is suitable for enviroment Installation category II  pollution degree.
The product is classed as "PERMANENTLY CONNECTED EQUIPMENT".
Product must be DIN rail mounted, inside a suitable enclosure providing environmental protection to IP65 or greater.
Dc supply must be derived from a local supply and not a distribution system.
Max relay contact rating 250 V AC @ 1 A (30 V DC @ 1A). Any circuit connected to a contact must be fused with a 2A (T) fuse.
To maintain CE EMC requirements , input and supply wires  must be less than 30 metres.
The product contains no serviceable parts , or internal adjustments. no attempt must be made to repair this product. Faulty units must be returned to supplier for repair.
This product must be installed by a qualified person. All electrical wiring must be carried out in accordance with the appropriate regulations for the place of installation.
Before attempting any electrical connection work, please ensure all supplies are switched off.

ABSOLUTE MAXIMUM CONDITIONS ( To exceed may cause damage to the unit):-

Supply Voltage

± 30 V dc  (Protected for over voltage and reverse connection)

Current with over voltage

± 200 mA

Input Voltage

± 5 V  between any terminals

Input Current

± 100 mA between terminals 7 & 10

Ambient

Temperature 

(-30 to 75) °C  Humidity (10 to 95) % RH (Non condensing)

Status Instruments Ltd,  Status Business Park,  Gannaway Lane,  Tewkesbury,  Gloucestershire,  UK,  GL20 8FD
Web Page:  www.status.co.uk    Tel : +44 (0) 1684 296818    Fax:  +44 (0) 1684 293746   email : [email protected]

Every effort has been taken to ensure the accuracy of this document, however we do not accept responsibility for damage, injury, loss or expense resulting from errors and omissions, and we reserve the right of amendment without notice.

Important - Potentially Hazardous situations. Persons responsible for the installation and operation of this equipment must be fully aware of all 
aspects of this guide. Failure to follow the instructions can cause severe injuries and damage.

The following parameter can be configured by simply entering as prompted by 
the software package. 

· Input type  (K,J,E,N,T,R,S,mV,PT100,mA)
· Setpoint Relay 1 & 2 
· Hysterisis Relay 1 & 2
· Units      (°C, °F,  mV,  mA)
· Relay 1 & 2 Type (High or Low)

PRODUCT SPECIFICATION

mA

Universal Input

10

9

8

7

mV

+

+

-

-

PT100

+

-

Dual trip Output

SEM1630

1

2

V s

USB

+

-

+

-

3

12

4

5

6

n/o

n/c

c

n/o

n/c

c

Relay 1

Relay 2

11

SEM1630 USER GUIDE

DIN RAIL MOUNTED TRIP AMP
UNIVERSAL INPUT
DUAL Form C OUTPUT

RECEIVE AND UNPACKING

CONFIGURATION

Please refer to the product data sheet for full specification, available to down load at www.status.co.uk.

Please inspect the packaging and instrument thoroughly for any signs of transit damage. If the instrument has been damaged, please notify 
your supplier immediately.

SEM1630

USB LINK SOFTWARE

USB CABLE

Download @ 

www.status.co.uk

COMPUTER

Factory default:

   Input type 

= P

   Units 

= °C

 

   Relay 1 

= H

 

   Setpoint Relay 1

= 50

   Hysterisis Relay 2

= 1

   Relay 2

= H

 

   Setpoint Relay 2

= 50

   Hysterisis Relay 2

= 1

IMPORTANT The SEM1630 can be configured whilst connected and powered, but  a portable battery powered computer must be 
used to avoid the effects of ground loops.

Note: The power supply and USB port of this device share the same ground , care must be taken to ensure isolation between PC and ground. 
         This is best achieved by using a portable laptop or notebook PC.