Installation, Commissioning & Routine Gas Testing
FGD10A Oxygen / Toxic Gas Detector
TD18/002
Issue:
16
Change Note:
1904
Page 31
4.8.19. E : 30
– Password
Use this menu option to enable / disable the password feature.
Place the FGD10A in the password menu as follows:
•
Press the MENU to open the menu system.
•
Using the NEXT and PREVIOUS buttons, select menu option:
E:30
•
Press ENTER.
•
The display shows either
On
or
OFF
•
Press the UP button to select the desired setting.
•
Press ENTER to accept the setting.
Note: Pressing MENU instead of ENTER leaves the unit
without change.
•
Press MENU to return the instrument to its standard mode of
operation.
Note:
if the password is in operation then the user will be prompted with
PASS when ever the menu key is pressed. Pressing the MENU key
again will result in the restricted user access, i.e. only the zero and
span options will be available. Entering the correct password will
give access to the full menu facility.
4.8.20. E : 31
– Warm-up timer
The sensor goes through a stabilisation period when power is first applied.
This option allows the user to adjust the time that is applied before readings
are displayed / transmitted.
•
From the menu system select menu option:
E: 31
and press
ENTER.
•
Using the INCREASE and DECREASE buttons, set the
required warm-up time.
•
Press ENTER to store the new value.
Note: Pressing the MENU button rather than the ENTER button
exits without any change.