IMPORTANT - CE  &  SAFETY REQUIREMENTS 

Product must be mounted, inside a suitable enclosure providing environmental protection to IP65 or greater.

To maintain CE EMC requirements , input  wires  must be less than 3 metres.

The product contains no serviceable parts , or internal adjustments. no attempt must be made to repair this product. Faulty units must be returned to supplier for repair.

This product must be installed by a qualified person. All electrical wiring must be carried out in accordance with the appropriate regulations for the place of installation.

Before attempting any electrical connection work, please ensure all supplies are switched off.

ABSOLUTE MAXIMUM CONDITIONS ( To exceed may cause damage to the unit) :-

Supply Voltage

± 30 V dc  (Protected for over voltage and reverse connection)

Current with over voltage

± 100 mA

Input Voltage

± 3 V  between any terminals

Ambient

Temperature 

(-40 to 85) °C  Humidity (10 to 95) % RH (Non condensing)

SEM206/P USER GUIDE

SMART HEAD MOUNTED TRANSMITTER INPUT PT100
TWO WIRE (4 to 20) mA  

Every effort has been taken to ensure the accuracy of this document, however we do not accept responsibility for damage, injury, loss or expense resulting from errors and omissions, and we reserve the right of amendment without notice.

Important - Please read this document before any installing.

PRODUCT SPECIFICATION

RECEIVE AND UNPACKING

CONFIGURATION

Please refer to the product data sheet for full specification, available to down load at www.status.co.uk.

Please inspect the packaging and instrument thoroughly for any signs of transit damage. If the instrument has been damaged, please notify your supplier immediately.

The following parameter can be configured by simply entering as prompted by the software package. 

· Low range 
· High range
· Units      (°C, °F)
· Burnout (direction of output current on sensor burnout)

Factory default:
Low Range

= 0

High Range

= 100

Units

= °C 

Burnout

= UPSCALE

Input PT100

1

2

3

2 Wire (4 to 20) mA 

Output

SEM206 P

+

-


s

Loop
Load

+

-

IMPORTANT Do not attempt to configure the SEM206 P when connected to a loop supply.

COMMS

Download @ 

www.status.co.uk

SEM206 P

USB SPEEDLINK

COMPUTER

USB CABLE

STATUS USB CONFIG-UNIT

Red +

Black -

CONFIGURATOR