1.0

DESCRIPTION

The DM640X series of intrinsically safe battery powered temperature indicators are
designed to work with industrial standard temperature sensors. The DM640XP variant
accepts a RTD (pt100) sensor, while the DM640XTC accepts a thermocouple sensor.

The sensor type, temperature units and other flexible configuration settings are
selectable via a simple to use menu system, navigated by the use of three push-button
keys located on the rear of the display. This is described in detail further on in this guide.
The entire assembly is encapsulated into a cap that fits directly onto the Status SCH4
series of connecting heads. Please refer to the SCH4 data sheet for further information.

2.0

RECEIVING AND UNPACKING

Please inspect the packaging and instrument thoroughly for any signs of transit damage.
If the instrument has been damaged, please notify your supplier immediately.

3.0

SPECIFICATION @ 20 °C

DM640XP

Accuracy

±0.2°C ± 0.1% of reading (Plus sensor error)

Resolution

0.1 °C

Measuring range

(-100 to 800) °C

Stability

Zero 0.01°C /°C
Span 0.005%/°C

Sensor

3 wire Pt100 to BS EN 60751(adjustable), or Ni120

Lead effect

10

per leg insignificant effect

Units

°C (default) or °F

Sensor type

Pt100 (default) or Ni120

DM640XTC

Accuracy

± 0.1% of FS ± 0.5°C (plus sensor)

Resolution

0.1 °C

Measuring range

See table below

Stability

Zero 0.02°C /°C
Span 0.01%/°C

Cold Junction Accuracy

±0.05°C/°C

Units

°C (default) or °F

Sensor type

K (default), T, J, N, R, S, E, F

Sensor

Range (

°C

)

K

-200 to 1370

T

-210 to 400

J

-100 to 1200

N

-180 to 1300

R *

-10 to 1760

S *

-10 to 1760

E

-200 to 1000

F

-100 to 600

* For type R and S sensors accuracy only applies between 800 and 1760 °C

DM640X General

Display

4 digit LCD

Battery Life

> 1 year @ 20°C ambient

Battery type

special battery refer to section 4

Ambient Temperature

(-10 to 50) °C

ATEX Approval

Refer to section 6

EMC Approval

Tested to BS EN 61326

Mechanical

Low profile SCH4 Head ABS, IP67 rating when used with
base unit

Connection

Sensor three way screw terminal block to accept 18-22 AWG
wire

4.0

INSTALLATION AND WIRING

4.1 Configuration

Warning The DM640X configuration operation must not be performed in the
hazardous area, return unit to the safe area for this operation.

Fit the battery as described in section 4.4, then follow the simple configuration menu
shown on pages 3 & 4, using the INC, DEC and CYC key (

see Fig 2

) to navigate. This

procedure can be performe d with or without the sensor connected. If the DM640X has
been configured for ° F, then affix the °F legend to the front panel, over the °C symbol.

4.2 Enclosure

The SCH4 case offers various options for sensor entry. Please refer to the SCH4 data
sheet f or further details. The sensor may be fixed directly to the SCH4 housing, or
remotely connected using cable and gland. All external cabling/sensor entries must
maintain IP67 rating.

4.3 Wiring

The DM640X series is provided with a two part connector bl ock, this allows for the cap
assembly to be un-plugged from the sensor for maintenance, while in the hazardous
area. Refer to the internal product label

(Fig2)

for the correct sensor connection details.

On the DM640X TC version, to maintain correct operation of the automatic cold junction
correction, ensure the thermocouple wires are either connected directly into the terminal
block or connected using the correct type of thermocouple extension wires.
On the DM640XP variant ensure three sensor wires are of the same type and length.
Cable length must be no greater than 10 metres to comply with CE certification.

4.4 Battery

BATTERY WARNING !!!

Important The battery must only be replaced in the safe area !!

Fire, Explosion and severe burn hazard. Do not Recharge, Crush,
Disassemble, Heat above 100°C (212°F), Incinerate or expose contents to
water.

Never short circuit the battery.

Disposal, the battery may be regulated by national and local regulations.
Please follow the instructions of the proper regulator.

The battery must only be replaced with a Tekcell SB- AA11 manufactured by
vitzo cell, available from either Status Instruments or your local distributor,
part number 28 -302-0036-00.

To install battery,:-

First gain access to the cap assembly by unscrewing the SCH4 cap retaining nut
and removing cap from base. Unplug the sensor connect

(fig 2 item3),

then trans-

port the cap assembly to the safe area.

Only when in the safe area, unscrew the two battery cover retaining SHCS screws

(fig 2 items 1)

using a suitable key. Then remove the cover

(fig 2 item 2).

To remove a fitted battery

(fig 2 item 6),

ease out the positive end of the battery

from the holder, using a screw driver blade.

To fit battery, insert battery negative into the spring contact end of the battery
holder, then press battery into place. See

fig 2

for correct polarity.

Replace the battery cover

(Fig 2 item 2)

ensure it is fitted the correct way

,

secure

with the two SHCS retaining screws

(fig 2 item 1).

Ensure unit is operating correctly, then transport cap to the application in the
hazardous area.

Re-connect sensor plug

(fig 2 item 3),

fit cap onto base and secure with nut.

The DM640X contains a battery monitoring system. When the battery approaches the
end of its lifetime (over 1 years under normal conditions), the display will toggle the
message “LO BAT”.

DM640XP & DM640XTC

Intrinsically Safe Battery

Powered Digital Thermometers

Designed, manufactured and supported by:

           

     

456 Park Avenue

     

Scotch Plains, NJ  07076

         

 Tel: 800-700-3272 Fax: 800-700-5468

Email:

  [email protected]

Every effort has been taken to ensure the accuracy of this specification, however we do
not accept responsibility for damage, injury, loss or expense resulting from errors and
omissions, and we reserve the right of amendment without notice

Summary of Contents for DM640X Series

Page 1: ...nected using cable and gland All external cabling sensor entries must maintain IP67 rating 4 3 Wiring The DM640X series is provided with a two part connector block this allows for the cap assembly to be un plugged from the sensor for maintenance while in the hazardous area Refer to the internal product label Fig2 for the correct sensor connection details On the DM640X TC version to maintain correc...

Page 2: ...Be used in gas groups Group A propane Group B ethylene Group C hydrogen Allowable temperature class T4 135 C Tamb 20 to 50 C 6 1 ATEX Mark The DM640X P and DM640X TC product labels carry the following information Front Panel Label Manufacturer Status instruments Ltd Type DM640X P DM640X TC Explosive protection mark CE mark Approval II 1 G D EEx ia IIC T4 Certification reference TRL06ATEX11100X Int...

Page 3: ...he number entered here Cycle around menu PASS 88 88 If non zero the user will be prompted for this number in order to enter the menu from run time If no buttons are pressed for a minute or more the device assumes run time mode The LCD shows the temperature if the input is in range or shows or to indicate over under range In order to access menu configuration mode the user must pressENTer followed ...

Page 4: ...he user will be prompted for this number in order to enter the menu from run time If no buttons are pressed for a minute or more the device assumes run time mode The LCD shows the temperature if the input is in range or shows or to indicate over under range In order to access menu configuration mode the user must press ENTer followed immediately by CYCle In order to exit the menu and return to run...