12 PROsine 2.5/3.0 Advanced Control System (ACS) Owner’s Manual
4. Troubleshooting
Should a fault occur, the fault LED will illuminate and an error code will be
displayed in the LCD. These error codes will over-ride any other menu items
being displayed. The following table lists the error codes, likely causes and
suggested solutions.
Error
Code
Description of Fault
Cause
Solution
000, 255
No Fault
There has been no fault since
the PROsine has been turned
ON.
001
Battery Temperature is too
high or too low
1. Room temperature around
the batteries is too high or
too low.
2. Faulty battery causes self
heating.
3. Faulty connection of
battery temperature probe.
1. Keep the temperature
around batteries moderate.
In cold weather, try a
Battery Heating Blanket.
2. Replace the faulty battery.
3. Check connections /
replace probe.
002
Battery Voltage is too low
1. Discharged battery.
2. Old or faulty battery.
3. Battery cables to the
PROsine Inverter•Charger
are too small, too long, or
there is a loose connection.
1. Charge battery.
2. Check if battery can hold
the charge by measuring the
Voltage at the battery
terminals when the battery
is discharging.
3. Check cables.
003
Battery Voltage is too high
1.
External charger or
alternator has output
voltage greater than 16 V.
2. The PROsine
Inverter•Charger is
connected to a 24V battery
(two batteries in series).
1. Correct external charging
source.
2. Re-wire batteries to give
the correct input voltage
(12 Volts).
006,065
Micro Processor
communication error
Remote display cable is
pinched or has loose
connection.
Unplug all cables from
REMOTE OUT Jacks on side
of PROsine. If problem
persists, call Statpower.