SANDBLASTER
®
Self-Cleaning Commercial Gas Water Heaters
MODEL
NUMBER
GAL
CAP.
INPUT
PER
HOUR
NATURAL/
PROPANE
FIRST
HOUR
RATING
100°F
RISE
40°
100°
140°
SBD30 150 NE
32
150,000
167
364
145
104
SBD30 199 NE
32
199,000
216
485
194
139
RECOVERY – GALLONS
PER HOUR AT °F TEMPERATURE RISE
MODEL
NUMBER
A
B
C
D
E
F
G
H
GAS
CONN.
WATER
CONN.
APPROX.
SHIPPING
WEIGHT
(LBS.)
SBD30 150 NE
45
40
27-3/4
32-1/4
15-3/4
5
6-1/2
6
3/4"
1-1/2"
400
SBD30 199 NE
45
40
27-3/4
32-1/4
15-3/4
5
6-1/2
6
3/4"
1-1/2"
400
DIMENSIONS AND WEIGHT
CAPACITY, INPUT AND OUTPUT
BOOSTER
MODELS
B
E
F
C
D
H
G
A
1-1/2" NPI
OUTLET
1-1/2" NPI
INLET
CLEARANCE
1" NPI RELIEF
VALVE OPENING
15.2cm
1.5
3.8cm
SUGGESTED SPECIFICATION
Gas booster water heater(s) shall be State Sandblaster, Model Number ___________________, with
a 32-gallon storage capacity, an input rate of __________________ BTU/HR, _________________gas,
and a recovery rate of________ gallons per hour at a________ degree Fahrenheit temperature rise, and a
maximum hydrostatic working pressure of 160 psi.
Unit(s) shall have a fan-assisted combustion system, providing a power-induced draft of makeup air prior to
burner ignition. Unit(s) shall be equipped with intermittent electronic ignition with power on/off switch, which
shall provide flame failure response in less than one second. The burner for the unit(s) shall be easily
removable. Unit(s) shall be equipped with a factory-installed temperature and pressure relief valve, and a
2-3/4" x 3-3/4" tank inspection port.
The water heater tank shall be glass-lined and protected against premature failure in the following ways:
1. Against electrolytic corrosion by multiple, factory-installed anode rods.
2.Against failure due to overheating caused by the buildup of scale, film and other sediment by a
self-cleaning device,positioned inside the tank so that it directs the flow of inlet water in such a way
that microscopic particles of precipitated solids shall be kept in suspension and exhausted from the
water heater on that or successive hot water draws.
Unit(s) shall meet or exceed ASHRAE/IESNA 90.1-1999, and be design-certified by CSA International, according
to ANS Z21.10.3 standards governing storage-type water heaters.