background image

1

PLACE THESE INSTRUCTIONS ADJACENT TO HEATER

AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE.

COMMERCIAL GAS WATER HEATER

Glass-Lined Tank-Type Water Heater

Instruction Manual

PART NO. 196114-000

 INSTALLATION 

 OPERATION 

 SERVICE

 •

 MAINTENANCE 

 LIMITED WARRANTY

PRINTED IN U.S.A.  0903

  

CAUTION

TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION
RELATIVE TO YOUR SAFETY. PLEASE READ THOROUGHLY
BEFORE INSTALLING AND USING THIS APPLIANCE.

Summary of Contents for 196114-000

Page 1: ...ER Glass Lined Tank Type Water Heater Instruction Manual PART NO 196114 000 INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY PRINTED IN U S A 0903 CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLING AND USING THISAPPLIANCE ...

Page 2: ...t editions of the National Fuel Gas Code ANSI Z223 1 NFPA 54 in Canada CAN CSA B 149 1 00 Both are available from the Canadian Standards Association 8501 East Pleasant Valley Road Cleveland OH 44131 For Canadian customers 178 Rexdale Blvd Rexdale Toronto Ontario Canada M9W 1R3 The National Fuel Gas Code ANSI Z223 1 NFPA 54 is available from the National Fire Protection Association 1 Batterymarch P...

Page 3: ...CERTAIN CHEMICAL VAPORS SUCH CORROSION MAY RESULT IN FAILUREAND RISK OFASPHYXIATION Spray can propellants cleaning solvents refrigerator and air conditioning refrigerants swimming pool chemicals calcium and sodium chloride water softener salt waxes and process chemicals are typical compounds which are potentially corrosive Do not store products of this sort near the heater Also air which is brough...

Page 4: ... THE RISK IF LOCATION IN SUCH AN AREA CANNOT BE AVOIDED DO NOT INSTALL THIS WATER HEATER DIRECTLY ON A CARPETED FLOOR A FIRE HAZARD MAY RESULT Instead the water heater must be placed on a metal or wood panel extending beyond the full width and depth by at least 3 inches 76 mm in any direction If the heater is installed in a carpeted alcove or closet the entire floor shall be covered by the panel A...

Page 5: ...NSULT CAN CSA B149 1 00 KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE MATERIALS GASOLINEANDOTHERFLAMMABLES VAPORSAND LIQUIDS DO NOT OBSTRUCT THE FLOW OF COMBUSTION OR VENTILATINGAIR WARNING FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR COMBUSTION AND VENTILATION AN INSUFFICIENT SUPPLY OF AIR WILL CAUSE RECIRCULATION OF COMBUSTION PRODUCTS RESULTING IN AIR CONTAMINATION THAT MAY BE HAZARDOUS TO L...

Page 6: ...ent connection is not available and the vent pipe from the heater must be connected to a common vent with an oil burning furnace the vent pipe should enter the smaller common vent or chimney at a point above the large vent pipe FIGURE2 DRAFTHOOD The draft hood furnished with this heater must be installed without alteration Provision must be made if it is installed in confined space or a small room...

Page 7: ...ONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED WARNING TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES SEE TEMPERATURE REGULATION ON PAGE 11 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES SINGLETEMPERATURE Size the main gas line in accordance with Table 1 T...

Page 8: ...ptable for the purpose in locating the leaks DO NOT USE MATCHES CANDLES FLAME OR OTHER SOURCES OF IGNITION FOR THIS PURPOSE FIGURE4 GASPIPINGANDDIRTLEGINSTALLATION DISCONNECTTHE HEATERAND ITS MANUALGAS Shut off VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURINGANY SUPPLY PRESSURE TESTING EXCEEDING 1 2 PSIG 3 45 Kpa GAS SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED FROM THE HEATER FOR TEST PRESSURES OF ...

Page 9: ...R STEPS TO BE TAKEN Before lighting the pilot and operating the heater the following conditions must exist Entire system filled with water Air purged from all lines and no leaks gas and water All gas and water lines open PRECAUTIONS DO NOT USE THISAPPLIANCE IF ANY PART HAS BEEN UNDER WATER The heater must be replaced IF THE UNIT IS EXPOSED TO THE FOLLOWING DO NOT OPERATE HEATER UNTILALLCORRECTIVE ...

Page 10: ...el If you don t smell gas go to next step 6 Remove or open inner door located below gas control unit 7 Find pilot follow metal tube from gas control The pilot is located in front of the burner or on the right hand side of the burner 8 If you don t smell gas turn knob on gas control counter clockwise to PILOT position 9 Push in control knob all the way and hold down Immediately light the pilot with...

Page 11: ...settings to reduce scald hazards Valves for reducing point of use temperature by mixing cold and hot water are available Also available are inexpensive devices that attach to faucets to limit hot water temperatures Contact a licensed plumber or the local plumbing authority SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAILTO SHUTOFF TURN OFFTHE MAIN MANUALGAS Shut off VALVETO THE APPLIANCE Temperatur...

Page 12: ... rapid ignition and carryover of flame across entire burner 3 Give reasonably quiet operation during ignition burning and extinction 4 Cause no excessive lifting of flames from burner ports If preceding burner characteristics are not evident check for accumulation of lint or other foreign material that restricts or blocks the air openings to the heater or burner WARNING SOOT BUILD UP INDICATES A P...

Page 13: ...checked to determine if replacement is necessary Initially the anode rod is approximately 7 8 22mm in diameter with a 1 8 3mm diameter steel core wire running down the center of the anode material THE ANODE SHOULD BE REPLACED when the 1 8 3mm diameter core wire is visible as this means that the anode material has been expended in the control of corrosion NOTE Anode rod inspection may need to be ma...

Page 14: ...ling the tank bottom This too can result in condensation Condensation appearing in the vent pipe water dripping from draft diverter during heater operation is evidence of poor vent action Possible causes are too long a vent pipe or improper chimney operation 3 If the leakage is from the temperature and pressure relief valve or its discharge pipe it may represent a normal condition However see RELI...

Page 15: ...15 NOTES ...

Page 16: ...16 ...