1460/61 INSTRUCTION MANUAL
Page B-2
CLOCK CODE 9:
hourly correction -
none
12 hour correction - the RUN and RESET relays activate at 12:00:00 (AM and PM) for 2
seconds
CLOCK CODE 11:
hourly correction -
the RUN and RESET relays activate at XX:59:25 for 35 seconds
12 hour correction - none
CLOCK CODE 12:
hourly correction -
the RUN and RESET relays activate at XX:44:00 for 1 minute
12 hour correction - none
CLOCK CODE 13:
hourly correction - the RUN and RESET relays activate at XX:41:00 for 4 minutes
12 hour correction - none
CLOCK CODE 15:
minute impulse -
the RUN relay activates at XX:XX:58 for 2 seconds, except during the
hourly correction
hourly correction -
the RESET relay activates at XX:58:50 for 12 seconds
12 hour correction - none
CLOCK CODE 16:
minute impulse -
the RUN relay activates at XX:XX:58 for 2 seconds, except during the
hourly correction
hourly correction -
the RESET relay activates at XX:59:50 for 12 seconds
12 hour correction - none
CLOCK CODE 20:
minute impulse -
the RUN relay activates at XX:XX:58 for 2 seconds
hourly correction -
the RESET relay activates at XX:44:02 for 53 seconds; 53 cycles
beginning at XX:44:02 of the RUN relay activating for ½ second and then
deactivating for ½ second
12 hour correction - none
CLOCK CODE 21:
minute impulse -
the RUN relay activates at XX:XX:58 for 2 seconds
hourly correction -
the RESET relay activates at XX:58:01 for 52 seconds; 52 cycles
beginning at XX:58:01 of the RUN relay activating for ½ second and then
deactivating for ½ second
12 hour correction - none
CLOCK CODE 23:
minute impulse
- the RUN relay activates at XX:XX:58 for 2 seconds;
- the RESET relay activates at XX:XX:58 for 2 seconds for the following times:
XX:59:58 to XX:04:58
hourly correction -
52 cycles beginning at XX:59:01 of:
the RUN relay activates for ½ second and then deactivates for ½ second
12 hour correction - none