![Stahl SolConeX 8572/15 Series Operating Instructions Manual Download Page 26](http://html1.mh-extra.com/html/stahl/solconex-8572-15-series/solconex-8572-15-series_operating-instructions-manual_1357595026.webp)
Transport and Storage
8
241408 / 857260300010
2018-02-02·BA00·III·en·01
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
SolConeX compact flange socket
Series 8572/15
For further technical data, see www.r-stahl.com.
6
Transport and Storage
• Transport and store the device only in the original packaging.
• Store the device in a dry place (no condensation) and vibration-free.
• Do not drop the device.
Back-up fuse
without thermal
protection
16 A gG
with thermal
protection
35 A gG
Ambient conditions
Ambient temperature -50 to +65 °C,
-40 to +65 °C, optional (silicone-free)
The maximum rated operational current depends on the conductor
cross-section and the ambient temperature.
Mechanical data
Number of poles
2P +
¿
/ 1P + N +
¿
Enclosure material
Polyamide, glass fibre reinforced
Degree of protection IP66 acc. to IEC/EN 60529
Connection type
Screw terminals
Connection
cross-section
Weight
0.310 kg
Service life
> 5,000 switching cycles (electrical and mechanical) acc. to IEC/EN 60309-1
Tightening torque
Terminals: 1.2 Nm
Technical Data
Ambient
temperature
Ta
(
+45 °C
Ta
(
+55 °C
Ta
(
+65 °C
Conductor
cross-section
Rated operational current
4 mm
2
16 A
12 A
10 A
2.5 mm
2
16 A
12 A
10 A
1.5 mm
2
10 A
7 A
6 A
1 mm
2
8 A
6 A
5 A
0.75 mm
2
6 A
4 A
3 A
Solid
1 x 0.75 mm
2
to 2 x 4 mm
2
Finely stranded
1 x 0.75 mm
2
to 2 x 4 mm
2
Finely stranded with core end
sleeve
1 x 0.75 mm
2
to 2 x 4 mm