Linear Luminaire for Fluorescent Lamps
Series EXLUX 6001
8
Commissioning
Before commissioning, ensure the following:
• Check the mounting and installation.
• Inspect enclosure for damage.
• If necessary, remove foreign bodies.
• If necessary, clean the connection chamber.
• Check if the conductors have been inserted correctly.
• Check if all screws and nuts have been tightened firmly.
• Check if all drilled holes are closed.
• Check whether all the cable entries and stopping plugs have been tightened firmly.
• Check if all conductors have been clamped firmly.
• Check if the line voltage and the rated operational voltage are consistent.
• Check if the permissible conductor diameter for the corresponding cable entries have
been used.
• Check if the device is closed according to regulations.
• Check that there is no protective foil on the translucent cover.
9
Operation
9.1
Troubleshooting
Observe the following troubleshooting plan for troubleshooting:
DANGER
Explosion hazard due to incorrect installation!
Non-compliance results in severe or fatal injuries.
• Check the device for proper installation before commissioning.
• Comply with national regulations.
NOTICE
Malfunction or device damage caused by condensation.
Non-compliance can result in material damage!
• operate the luminaire continuously or periodically over extended periods of time.
• avoid thermal bridges.
Cause of error
Troubleshooting
The lamp was incorrectly inserted.
Insert the lamp correctly.
The lamp is defective.
Replace the lamp.
The control gear is defective.
Replace the control gear.
The switch is defective.
Replace the switch.
The lamp reached its end of service life.
Replace the lamp.