Technical Data
8
271489 / 8040621300
2019-04-15·BA00·III·en·00
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Installation Switch
Series 8040/11-V30
5
Technical Data
Explosion Protection
Global (IECEx)
Gas and dust
IECEx PTB 06.0025
Ex db eb ia ib [ia Ga] mb q IIA, IIB, IIC, T6 ... T4 Gb
Ex tb IIIC T80 °C, T95 °C, T130 °C Db
Europe (ATEX)
Gas and dust
PTB 01 ATEX 1105
E
II 2(1) G Ex db eb ia ib [ia Ga] mb q IIA, IIB, IIC, T6 ... T4 Gb
E
II 2 D Ex tb IIIC T80 °C, T95 °C, T130 °C Db
Certifications and certificates
Certificates
IECEx, ATEX, others on request
Technical Data
Electrical data
Rated operational
voltage
690 V AC, 220 V DC
Switching capacity
acc. to IEC/EN 60947-1; IEC/EN 60947-3; IEC/EN 60947-5-1:
Ambient conditions
Ambient temperature -20 to +60 °C (sealing material: NBR)
-60 to +60 °C (sealing material: silicone)
At ambient temperatures < -40 °C, special cable entries suitable for
low temperatures must be used, or the device must be positioned in a way that
the cable entries are mechanically protected. Please consult the manufacturer
if operating conditions are non-standard.
AC-1
AC-11
AC-15
DC-13
(L/R=300 ms)
690 V, 16 A
660 V, 2.5 A
415 V, 16 A
230 V, 0.4 A
500 V, 4 A
380 V, 6 A
220 V, 6 A
DC-11
(L/R=100 ms)
DC-11
(L/R=50 ms)
DC-11
(L/R=1 ms)
220 V, 0.4 A
220 V, 0.6 A
220 V, 1.0 A
110 V, 1.0 A
110 V, 1.6 A
110 V, 4.0 A
60 V, 4.0 A
60 V, 6.0 A