Pendant Light Fitting LED
Series 6470/5
7.3.2 Electrical connections
• Slide silicon hoses (2 or 4 pieces) included in delivery over single cores L and N.
• Insert connection cable into corresponding terminal blocks and fix it.
• Protective conductor is factory fitted to PE connection on the enclosure cover.
• Fix protective conductor of cover and connection cable to the enclosure.
• Close the cable entry.
• Securely install the installation cable and secure it against pulling out.
Connection terminals
Through wiring of the mains supply connection
Earth connection
Earth connection internal or external possible.
Ballast and ignitor are wired as delivered according to the lamp used.
No further installation work is required on these elements.
Standard:
Cage clamp terminal
Optional:
Cage clamp terminal
Clamping range:
0.75 to 4 mm
2
solid / finely stranded
(2 free clamping units
per pole available)
Clamping range:
1x 0.2 to 6 mm
2
(solid)
1x 0.2 to 4 mm
2
(finely stranded)
1x 0.25 to 6 mm
2
(finely stranded with
core end sleeves)
(2 free clamping units
per pole available)
Stripping length:
10 to 11 mm
Stripping length:
10 to 12 mm
16373E00
20508E00
Through wiring with 2.5 mm
2
cross section for max. 12 A.
L1
N
N
L1
L1
N
PE
L1
= phase
N
= neutral
conductor
PE
= protective
conductor