Compact Sheet-steel
Emergency Light Fitting
Series 6118/1
10.2 Indications
When connecting to the power supply
Initialisation within 30 seconds
After that, the LED display switches to the operating mode.
During normal operation
Blinking: 1 second on, 1 second off
Flashing: 0.25 seconds on, 0.75 seconds off
During emergeny light operation
The LED display is switched off.
10.3 Troubleshooting
Observe the following troubleshooting plan for troubleshooting:
Second Description
0 to 10 Function test green LED
10 to 20 Function test red LED
20 to 30 continuous operation
test state
green LED blinks - continuous operation test active
red LED blinks - continuous operation test not active
Green
Light fitting is ready for
operation
blinking
green
Light fitting is ready for
operation
Function or continuous operation test is
activated
Red
Error
Battery is defective or electric circuit is
interrupted
blinking red Error
Battery capacity is too low
flashing red Error
The lamp reached its end of service life or is
defective
blinking
green/red
Light fitting is ready for
operation No emergency
light operation
Emergency light operation is deactivated by
remote switch
Cause of error
Troubleshooting
The lamp was incorrectly inserted.
Insert the lamp correctly.
The lamp is defective.
Replace the lamp.
The ballast is defective.
Replace the ballast.
The switch is defective.
Replace the switch.
The lamp reached its end of service life.
Replace the lamp.
LED display red
The battery is defective.
Replace the battery.
The switch in the battery case is defective. Replace the switch.
The switch in the light fitting is defective.
Replace the switch.
LED display blinking red
The battery capacity is too low.
Replace the battery.