Technical data
19
Wall-mounting socket Type 7571/11 and plug Type 7571/12
eng
lish
5.3.2 Colour coding and earthing contact socket configuration
Number of
pins
Frequency
[Hz]
Rated operating
voltage
[V]
Identification
colour
Position of the
earthing
contact socket
7571/..-4..
3P+
50-60
200-250
blue
9 o’clock
380-415
red
6 o’clock
60
440-460 1) red
11 o’clock
50-60
480-500
black
7 o’clock
600-690
black
5 o’clock
100-300 2) > 50
green
10 o’clock
7571/..-5..
3P+N+
50-60
120/208-144/250
blue
9 o’clock
200/346-240/415
red
6 o’clock
277/480-288/500
black
7 o’clock
347/600-400/690
black
5 o’clock
60
250/440-265/460 1) red
11 o’clock
Table 5-4: Colour coding and configuration are assigned as per IEC 60 309-2 pin and sleeve
standard that makes the mating of plugs and receptacles of different voltages and
frequencies impossible.
1) Chiefly for ship’s wiring
2) Frequencies
≥
100 Hz lead to higher heating behaviour. This must
be compensated by a max. ambient temperature of
≤
40 °C, a T5