Faults
Fault 223: Burner Louver Did Not Close for Pilot Ignition (See Fault 20)
Indicates that the burner louver did not close for pilot ignition (Fault 223 and Fault 20 indicate the same
failure. Fault 223 is an early warning for Fault 20. Fault 20 can take up to 5 minutes to occur).
Causes
Troubleshooting
Fixes
• Faulty louver actuator.
• Test in “Manual Mode” to see
if louver actuator moves. Go to
Menu > Operations >
Manual
Mode. In Manual Mode verify
that internal louver actuator
switches are working by
observing relay ABD-1 and ABD-2
cycle on/off when the louver is
open/closed respectively.
• If a spare louver actuator is
available, swap it to see if it
works.
• Replace louver actuator (check
other causes before buying a new
component).
• Temporary fix: Reset louver
actuator by unplugging louver
actuator and then plug it back in.
• Faulty wiring path from louver
actuator switches to ABD-1 or
ABD-2.
• Obstructed path of the louver
actuator.
• Remove actuator and manually
move the louver to feel if there is
any resistance or obstructions.
• Remove obstructions.
• Blown fuse (F1) or (F9) in Panel
3.
2015-16 machines: F1 or F11.
• Visually inspect the fuses.
• Replace fuse.
• Blown fuse (F8) in Panel 2.
• Visually inspect the fuse.
• Replace fuse.
• Faulty relay ABD-2.
• Swap with relay ABD-1 to see if
it works.
• Replace relay.
• PLC and touch screen not
version 3.1 or higher
(Version 2.3 or higher for 2015-
2016 machines).
• Check which version is being
used by going to Menu >
Information > Version.
• Update to Version 3.1 or higher
on the PLC and Touch Screen
(Version 2.3 or higher for 2015-
2016 machines).
• Faulty wiring.
• Inspect wiring for continuity,
voltage, and ground.
• Replace/Repair faulty wiring.