User Manual
Universal Serial/PROFIBUS DP Gateway
GT200-DP-RS
WWW.SSTCOMM.COM
14
Note: The GT200-DP-RS will apply the new configuration after entering Run mode. After downloading, the
software will ask to switch mode. You can also switch mode manually by setting button, referring to
.
4.2.2 Configure by STEP7 (PROFIBUS Integrated Configuration
Software)
The DP Integrated Configuration mode allows users to configure the GT200-DP-RS in PROFIBUS integrated
configuration software, such as STEP7 or TIA Portal.
To apply this mode, please change the configuration mode of the GT200-DP-RS in SST-MPG-CFG software to
“via PROFIBUS DP Integrated Configuration Software” and download the configuration. The LED should
display “-P” that indicates the GT200-DP-RS is in DP Integrated Configuration mode.
The following steps give an example of the STEP7 configuration process.
1. Double click on the “Hardware” to open the hardware configuration window of your project.
2. Register the GSD file. On the top menu bar, select “Options” >> “Install DSG File...” and install the GSD
files of GT200-DP-RS. For detailed description of the GSD files, please see