SSP North AB
30/08/2018
Manual V2f
49
Display LEDs
Code
Name
Description
Solution
2
0x0002 NO_NETWORK_ID
No configured
network ID.
Download a new
configuration to
the unit.
1 & 4
0x0009 SETTINGS_SERIAL_NUMBERS Invalid serial number
settings.
Download a new
configuration to
the unit.
2 & 4
0x000A SIO_OVER_CURRENT_IRQ
Overcurrent
protection. There is
an output connected
directly to ground.
Disconnect the
faulting terminal.
1 & 2 & 3 & 4 0x000F BAD_CFG_NODE_NR
Invalid node number
settings.
Download a new
configuration to
the unit.
9
0x0100 PWR_SUPPLY_TOO_HIGH
Voltage is higher
than the configured
max voltage.
Check power
supply, and
project settings.
9 & 2
0x0102 PWR_SUPPLY_TOO_LOW
Voltage is lower than
the configured min
voltage.
Check power
supply, and
project settings.
15 & 16 & 1-8 0xC001
to
0xC0FF
USER_FATAL_ERROR
User fatal error
triggered from logic.
See program
logic for this
unit.
Table 11.1: Fatal error codes and descriptions