background image

Closed lead batteries consist of cells, which do not 

allow refi lling with water over the entire service life. 

Relief valves are used as sealing plugs, which can 

only be opened by destruction.

1. Commissioning

Before the commissioning, all blocks must be checked 

for mechanical damage, correct polarity, and tight seat 

of the connectors. The batteries must not be installed 

at more than 2,000m. The valve cover, which covers 

the relief valve, must not be taken off or taped over. 

The following torques apply to screw connections:

If  necessary,  the  pole  covers  are  to  be  placed  on. 

Connect  the  battery  to  the  DC  supply  with  correct 

polarity when the charging device is switched off and 

consumers are disconnected (positive pole on posi-

tive connecting clamp), switch on the charging device 

and charge according to Point 2.2.

2. Operation

EN IEC 62485-2 applies to the design and operation of 

these batteries. The battery must be installed so that 

between the individual blocks an environmental tem-

perature difference of > 3K cannot occur.

2.1 Discharging

The  end-point  voltage  of  the  battery  must  not  fall 

below the discharge current assigned to it. As long 

as there are no special instructions from the manu-

facturer, no more than the nominal capacity must be 

taken. After discharge, also partial discharge, it must 

be immediately charged. 

2.2 Charging

All  charging  methods  can  be  used  with  their  limit 

values  according  to  DIN  41773-1  (IU  characteristic 

curve).  Depending  on  the  charging  device  design 

and charging device characteristic curve, alternating 

currents fl ow through the battery during the charging 

process,  which  are  superimposed  onto  the  direct 

current (< 0.1C(A) effective ripple). These superim-

posed alternating currents and the reactions of the 

consumers  lead  to  an  additional  warming  of  the 

battery  and  strain  on  the  electrodes  with  possible 

resulting damage (see Point 2.5). Depending on the 

system,  charging  can  take  place  with  the  following 

operating  modes  (according  to  VDE  0510-485-2). 

(Batteries must not be charged upside down!)

a) Standby parallel and buffer operation

Here the consumers, the DC source and the battery 

are continually switched on in parallel. Thereby, the 

charging voltage is the operating voltage of the bat-

tery and at the same time the system voltage. For 

standby parallel operation the DC source is capable 

at  all  times  of  supplying  the  maximum  consumer 

current  and  battery  charging  current.  The  battery 

only supplies current when the AC source fails. The 

charging voltage to be set is 2.275V ± 1% (20 °C) x 

the number of cells in series connection, measured 

on the end poles of the battery. In buffer operation, 

the DC source is not able to always supply the maxi-

mum consumer current at all times. The consumer 

current intermittently exceeds the nominal current of 

the DC source. During this time the battery supplies 

current.  It  is  not  always  charged  at  all  times,  how-

ever, the maintenance charge voltage of 2.275V/cell 

at 20 °C x number of cells in series connection is 

suffi cient  to  ensure  a  recharge.  A  consumer-and-

cell-number-dependent  tuning  should  be  done  in 

individual cases with the battery manufacturer.

b) Switching mode

The battery is disconnected from consumers during 

charging. To shorten the recharging time, in the fi rst 

charging step the battery is charged with a voltage 

of  2.35–2.40V/cell  up  to  a  point  in  time  when  the 

charging current drops to 0.07C(A)(t

1

). The charging 

time of the fi rst phase is measured to reach this va-

lue. During the second phase of the recharging, a vol-

tage of 2.35–2.40V/cell is used, whereby the rechar-

ging time of the second phase should be 50% of the 

fi rst phase (t

2

 = 0.5t

1

). When exceeding t > t

1

 + 0.5t

1

the voltage is reduced to the maintenance voltage of 

2.275V/cell (± 1%) at 20 °C.

c) Battery mode (charge/discharge mode)

The consumer is only fed from the battery. The char-

ging  method  is  user-dependent  and  to  be  agreed 

upon with the battery manufacturer.

2.3 Maintaining the full charge condition 

(maintenance charging) 

Devices with the specifi cations according to DIN 41773-1 

must be used. They must be set so that the cell voltage 

has an average of 2.275V ± 1%.

2.4 Supplementary and equalising charge

Before  the  fi rst  commissioning,  a  supplementary

charge  of  the  batteries  must  be  carried  out  and 

logged. Equalising charges are required after deep 

discharge  and  insuffi cient  charging.  The  battery 

surface temperature must not exceed 45 °C during 

this; if necessary, the charging must be interrupted 

or switched to charge maintenance. The end of the 

supplementary/equalising  charge  is  reached  when 

the  charge  voltage  and  charge  current  no  longer 

show any change within two hours. Batteries, which 

are installed retroactively in a battery network as a re-

placement, must be fully charged before installation.

2.5 Superimposed alternating current (AC)

During  the  recharging  up  to  2.4V/cell  according  to 

the operating modes Point 2.2, the effective value of 

the AC may be briefl y 0.1C(A). After recharging and 

further charging (maintenance charging) in standby 

parallel  operation  or  buffer  operation,  the  effective 

value of the AC must not exceed 2A/100Ah nominal 

capacity.

2.6 Charging currents

In  standby  parallel  operation  or  buffer  operation 

without recharge step, the charging currents are not 

restricted. The charging current should be 10A to 20A 

per 100Ah nominal capacity (reference value). In cycle 

operation, the charging current should not exceed 

0.3C(A) (30A/100Ah).

2.7 Temperature

The recommended operating temperature range for 

lead batteries is 10 °C to 30 °C. The ideal operating 

• Nominal voltage U

N

:

cells 2V  blocks 6V  blocks 12V

• Nominal capacity C20:

20-hour discharge

• Nominal temperature T

N

:

20 °C

• Reduction factors:

according to EN IEC 62485-2

• Nominal discharge current:  I

N

 = I

20

C

N

/20h

Battery manufacturer: SSB Battery  

Model: SBH

Installation by:

on:

Commissioning by:

on:

Safety labels applied by:

on:

Nominal data

M5

M6

M8

M10

2–3Nm

4–5.5Nm

5–6Nm

14–22Nm

Observe user manual and place visibly near the battery!

Only work on the battery after instruction by technical specialists!

Smoking prohibited! Do not bring an open fl ame, embers or sparks near the battery, 

as there is a risk of explosion and fi re!

Wear safety glasses and protective clothing when working on batteries!

Observe the accident prevention regulations as well as EN IEC 62485-2!

Flush out or rinse off acid splashes in the eyes or on the skin with ample clean water. 

Afterwards, see a doctor immediately. Wash acid-contaminated clothing with water!

Risk of explosion and fi re, prevent short circuits! Caution! Metal parts of the batteries 

are always live, therefore do not place any foreign objects or tools on the battery!

Electrolyte is highly corrosive! In normal operation contact with the electrolytes is 

practically excluded. If you have come into contact with the electrolyte, please rinse 

thoroughly with water and see a doctor!

Block batteries/cells have a high tare weight! Make sure of secure placement! 

Only use suitable transport equipment.

Recyclable commodity; does not belong in domestic waste! 

Non-compliance with the user manual, the non-use of original spare parts for repairs or 

unauthorised interventions void the warranty claims.

Return to the manufacturer

Used batteries with this symbol are recyclable commodities and must be sent to the 

recycling process. Used batteries, which are not sent to the recycling process, must be 

disposed of as hazardous waste, in compliance with all regulations.

1

User Manual

Maintenance-free lead batteries in nonwoven 
technology, valve controlled (VRLA/AGM)
Type OGiV: SSB SBH

Reviews: