All-in-one solar charge inverter V1.0 9
2.2 Wiring specifications and circuit breaker selection
Wiring and installation must comply with national and local electrical codes.
Recommended PV array wiring specifications and circuit breaker selection: Since the output current of
the PV array is affected by the type, connection method and illumination angle of the PV module, the
minimum wire diameter of the PV array is calculated according to its short-circuit current; refer to the
short-circuit current value in the PV module specification (the short-circuit current is constant when the
PV modules are connected in series; the short-circuit current is the sum of the short-circuit currents of
all PV modules connected in parallel); the short-circuit current of the PV array shall not exceed the
maximum input current.
Refer to the table below for PV input wire diameter and switch:
Models
Recommended PV
wiring diameter
Maximum PV
input current
Recommended circuit
breaker type
HYP4850S100-H
6mm2/10AWG
22A
2P—25A
HYP4850U100-H
6mm2/10AWG
22A
2P—25A
Note:
The voltage in series shall not exceed the maximum PV input open circuit voltage.
Refer to the table below for recommended AC input wire diameter and switch:
Models
Recommended AC
input wiring diameter
Maximum
bypass input
current
Recommended circuit breaker
type
HYP4850S100-H
10mm2/7AWG
40A
2P—40A
HYP4850U100-H
10mm
2
/7AWG
63A
2P—63A
Note:
There is already an appropriate circuit breaker at the Mains input wiring terminal, so it is not
necessary to add one more.