All-in-one solar charge inverter V1.0 47
discharging time
53
Sectional discharge
function
[53] DIS Default
Disable this Function
[53] ENA
After the sectioned discharge function is
enabled, the power supply mode will change to
AC1ST and the system will switch to battery
inverter power supply only during the set
discharge period or when the mains power is off
54
Current date
setting
[54] 00:00:00 Default Set Range: 00:01: 01-99:12:31
55
Current time
setting
[55] 00:00:00 Default Set Range: 00:00: 00-23:59: 59
56
Leakage protection
function
[56] DIS Default
Disable this Function
[56]ENA
Enable leakage protection function
57
Stop charging
current
[57] 2A default
Charging stops when the default charging
current is less than this setting
58
Discharge alarm
SOC setting
[58] 15% default
SOC alarm when capacity is less than this set
value (valid when BMS communication is normal)
59
Cut-off discharge
SOC Settings
[59] 5% default
Stops discharging when the capacity is less than
this setting (valid when BMS communication is
normal)
60
Cut-off charge SOC
Settings
[60]100% default
Stops charging when capacity is greater than or
equal to this setting (valid when BMS
communication is normal)
61
Switch to mains
SOC Settings
[61] 10% default
Switch to mains when capacity is less than this
setting (valid when BMS communication is
normal)
62
Switch to inverter
output SOC
Settings
[62] 100% default
Switches to inverter output mode when capacity
is greater than or equal to this setting (valid
when BMS communication is normal)