All-in-one solar charge inverter V1.0 46
charging time
42
2-section start
charging time
[42] 00:00:00 Default Set Range: 00: 00-23: 59: 00
43
2-section end
charging time
[43] 00:00:00 Default Set Range: 00: 00-23: 59: 00
44
3-section start
charging time
[44] 00:00:00 Default Set Range: 00: 00-23: 59: 00
45
3-section end
charging time
[45] 00:00:00 Default Set Range: 00: 00-23: 59: 00
46
Sectional charging
function
[46] DIS Default
Disable this Function
[46] ENA
After the sectioned charging function is enabled,
the power supply mode will change to BT1ST,
and system will enable the mains power charging
only in the set charging period or battery over
discharge; If the sectioned discharge function is
enabled at the same time, the power supply
mode of the system will change to AC1ST, which
only enable the mains charging in the set
charging period, and switch to the battery
inverter power supply mode in the set discharge
period or when the mains power is off
47
1-section start
discharging time
[47] 00:00:00 Default Set Range: 00: 00-23: 59: 00
48
1-section end
discharging time
[48] 00:00:00 Default Set Range: 00: 00-23: 59: 00
49
2-section start
discharging time
[49] 00:00:00 Default Set Range: 00: 00-23: 59: 00
50
2-section end
discharging time
[50] 00:00:00 Default Set Range: 00: 00-23: 59: 00
51
3-section start
discharging time
[51] 00:00:00 Default Set Range: 00: 00-23: 59: 00
52
3-section end
[52] 00:00:00 Default Set Range: 00: 00-23: 59: 00