All-in-one solar charge inverter V1.0 43
23
Overload
Automatic Restart
[23] DIS
Overload automatic restart is disabled. If
overload occurs, the output will be shut down,
and the machine will not be restarted.
[23] ENA Default
Enable overload auto restart. If overload occurs,
shut down output, delay the machine for 3 min
and then restart the output. After 5 times in total,
no startup will be resumed.
24
Auto restart upon
over-temperature
[24] DIS
Over-temperature automatic restart is disabled.
If over-temperature occurs, the output will be
shut down, and the machine will not be restarted
for output.
[24] ENA Default
Enable automatic restart upon over-temperature.
If over-temperature occurs, shut down output,
and restart output after the temperature has
dropped.
25
Buzzer Alarm
[25] DIS
No Alarm
[25] ENA Default
Enable alarm
26
Mode Change
Reminder
[26] DIS
Alarm is disabled when the status of the main
input source has change.
[26] ENA Default
Alarm is disabled when the status of the main
input source has change.
27
Inverter Overload
to Bypass
[27] DIS
Automatic switch to Mains Power is disabled
when the Inverter is overloaded.
[27] ENA Default
Automatic switch to Mains Power when the
inverter is overloaded.
28
Current of charging
under grid
electricity
[28] 60A Default
AC output 230Vac, with the Set Range of 0~60A
28] 40A Default
AC output 120Vac, with the Set Range of 0~40A
30
RS485 Address
Setting
[30] 1 Default
RS485 communication address can be set within
the range of 1~254