All-in-one solar charge inverter V1.0 39
[01] PV1ST
Solar First Mode: switch to Mains Power when PV
has failed or battery is lower than Parameter [04]
Set Value.
02
Output Frequency
[02] 50.0 Default
Bypass self-adaptation; when the mains is
connected, it automatically adapts to the mains
frequency; when the mains is disconnected, the
output frequency can be set through this menu. The
default output frequency of the 230V machine is
50HZ, and the 120V machine is 60HZ.
[02] 60.0
03
AC Input Voltage
[03] UPS Default
The input mains voltage range of 230V machine
is 170~280V
Mains input voltage range of 120V machine:
90~140V
[03] APL
The input mains voltage range of 230V machine
is 90~280V
Mains input voltage range of 120V machine:
90~140V
04
Battery to Mains
[04] 43.6V Default
When the Parameter [01] = BT1ST/PV1ST, the
battery voltage is lower than the set value, and
the output is switched from inverter to Mains
Power, and the set range is 40V~52V.
05
Mains to Battery
[05] 56.8V Default
When the Parameter [01] = BT1ST/PV1ST, the
battery voltage is higher than the set value, and
the output is switched from mains to inverter,
and the set range is 48V~60V.
06
Charging mode
[06] Hybrid Default
Hybrid charging by PV and under utility grid give
priority to PV, and use utility grid for
supplementary if PV energy is insufficient. When
the PV energy is sufficient, the utility grid will
stop charging. Note: PV and utility grid are
available for charging at the same time only
when the bypass output is loaded, and only PV
charging can be activated when the inverter is