8. Technical Parameter
Model
HF4830S60-H
MF4830S60-H
HF4850S80-H
MF4850S80-H
AC mode
Rated input voltage
220/230Vac
Input voltage range
(170Vac~280Vac) ±2%
(90Vac-280Vac) ±2%
Frequency
50Hz/ 60Hz (auto-sensing)
Frequency range
47±0.3Hz ~ 55±0.3Hz (50Hz);
57±0.3Hz ~ 65±0.3Hz (60Hz);
Overload/short- circuit
protection
Breaker
Efficiency
>95%
Conversion time
10ms (Typical value)
(Bypass and inverting)
AC reverse flowing
protection
yes
Maximum bypass overload
current
40A
Inverting mode
Output voltage waveform
Pure sine wave
Rated output power (VA)
3000
(
2600/2700/3000
)
5000(4350/4500/4800/5000)
Rated output power (W)
3000
(
2600/2700/3000
)
5000(4350/4500/4800/5000)
Power factor
1
Rated output voltage (Vac)
230Vac(200/208/220/240Vac Settable)
Output voltage error
±5%
Output frequency range (Hz)
50Hz ± 0.3Hz
60Hz ± 0.3Hz
Efficiency
>90%
Overload protection
(102%<load<125%) ±10%: reporting error and turn off the output after 5 minutes;
(125%<load<150%) ±10%: reporting error and turn off the output after 10 seconds;
Load>150% ±10%: reporting error and turn off the output after 5 seconds;
Peak power
6000VA
10000VA
Loaded motor capacity
2HP
4HP
Output short-circuit
protection
Breaker
Specification of bypass
breaker
40A
Rated battery input voltage
48V (minimum start voltage 44V)
Battery voltage range
40.0Vdc~60Vdc ± 0.6Vdc (undervoltage alarm/turnoff voltage/overvoltage
Solar Energy Storage Inverting & Control All-In-One Machine 33