Page 1 of 4
IN019-1 Rev B
( RB110 )
Page 1: ...Page 1 of 4 IN019 1 Rev B RB110 ...
Page 2: ...n the outlet of the dryer and the inlet of the fan Connect the outlet of the fan to the termination ductwork Seal the connections with duct tape or similar means 3 0 Automatic Pressure Switch Installation The pressure switch must be mounted vertically on a wall surface as near the outlet of the dryer as possible Mount the duct probe through the duct and connect with tubing provided to the pressure...
Page 3: ...heck the following The auxiliary fan may be generating sufficient negative pressure to overcome the positive pressure generated by the dryer This can be verified with a sensitive pressure measuring device or with an AC voltmeter at the pressure switch Relocate the auxiliary fan further away from the dryer and recheck 6 0 Maintenance Lint may accumulate inside the fan impeller and housing or on the...
Page 4: ...arranty is contingent on installation of the Kit in accordance with the instructions provided This Warranty does not apply where any repairs or alterations have been made or attempted by others or if the unit has been abused or misused Warranty does not include damage in shipment unless the damage is due to the negligence of Spruce Spruce is not responsible for installation removal or delivery cos...