16
Anybus Option Modules
4.2.1.3
LINK/Activity LED
LED State
Description
Off
No link
Green
Link
Green, flickering
Activity
4.2.2 Cyclic Data
To transfer Cyclic Data (Process Data), configure the PLC to match the number of Input and
Output words from the number of used FIELDBUS
GET
GET
FROM
FROM
s and
GOTO
GOTO
s.
The GSD file specifies nine INPUT modules and nine OUTPUT modules:
INPUT 1 Word; INPUT 2 Words; ..................................; INPUT 9 Words
OUTPUT 1 Word; OUTPUT 2 Words; ..................................; OUTPUT 9 Words
Select one INPUT module and one OUTPUT module to match the
GET
GET
FROM
FROM
s and
GOTO
GOTO
s
(respectively).
4.2.3 Acyclic Data
Parameters can be accessed acyclically from the PLC using Record Data read/write services.
Index
= parameter number
Slot
= 0
SubSlot
= 1
Size
= 2 (bytes)
For example:
409)SUMMER
409)SUMMER
1
1
INPUT
INPUT
2
2
is
Index:Slot:SubSlot:Size 409:0:1:2
4.2.4 Electronic Data Sheet
PROFINET GSDML files:
GSDML-V2.35-SPRINT-Electric-20220425
PLX or JLX
M40
GSDML-V2.25-SPRINT-Electric-M30-20220425
PLX or JLX
M30 2-Port
GSDML-V2.0-SPRINT-Electric-M30-1P-20220425
PLX or JLX
M30 1-Port