8 Options
Options
Consider the following changes to tune/improve the performance of the drive/system.
8.1 Torque Control Mode
The drive can control the torque (current) of the motor, instead of the speed (volts), by
allowing an external input to clamp the current demand. NOTE: The speed loop then
provides the current demand, and hence the speed loop must always be asking for more
current than the clamp level. This technique gives automatic over-speed limiting.
Establish the correct operating limits by commissioning first in speed mode. Then implement
torque control by moving the SPEED / 2Q / 4Q link from SPEED to the required TORQUE
position (2Q or 4Q) and apply an appropriate torque control voltage to T6.
TORQUE/SPEED JUMPER:
This is a 3-position jumper controlling the function of Terminal 6
(AUX). A schematic is shown below:
The 2Q TORQUE
clamp operates in 1Q
and 2Q on the positive
current only.
The 4Q TORQUE
clamp operates in
all 4 quadrants on
positive and negative
currents.
The 4Q TORQUE mode
can be used for load
sharing by inputting
the modulus current
signal from SP69 on a
master drive.
C
D
A
B
6
AUX
speed feedback
speed demand
+
-
-
-
0.5
error amp
inverter
current demand signal
current demand
/-7.5 V
A/B/C/D electronic
switches
-ve clamp
+ve clamp
speed
input
4Q TORQUE
2Q TORQUE
SPEED
POS I
MOTOR
FWD
NEG I
BRAKE
REV
1
2
3
left
hand
P6
right
hand
mode
P10
mode
jumper
2Q
3Q
4Q
1Q
speed+
generating
clockwise
(brake)
motoring
anticlockwise
(motor)
QUADRANT DIAGRAM
NEG I
POS I
current demand signal
SCHEMATIC OF STALL TIMER
-
+
-
+
-
+
DETECTOR
TIMER LAMP
TO LATCH
TIMER
(integrator)
INTEGRATION
0 V
-2.5 V
-5.25 V
-7.5 V
50%
150%
105%
R4
MAX CURRENT
motoring
clockwise
(motor)
generating
anticlockwise
(brake)
volts
current
setpoint
ramp
T13
T14
STOP
START
0 V
T3
speed setpoint
XIP T64
+24 V
RL2
RL2
START RELAY
OPTIONAL START (ramp to zero)
C
D
A
B
6
AUX
speed feedback
speed demand
+
-
-
-
0.5
error amp
inverter
current demand signal
current demand
/-7.5 V
A/B/C/D electronic
switches
-ve clamp
+ve clamp
speed
input
4Q TORQUE
2Q TORQUE
SPEED
POS I
MOTOR
FWD
NEG I
BRAKE
REV
1
2
3
left
hand
P6
right
hand
mode
P10
mode
jumper
2Q
3Q
4Q
1Q
speed+
generating
clockwise
(brake)
motoring
anticlockwise
(motor)
QUADRANT DIAGRAM
NEG I
POS I
current demand signal
SCHEMATIC OF STALL TIMER
-
+
-
+
-
+
DETECTOR
TIMER LAMP
TO LATCH
TIMER
(integrator)
INTEGRATION
0 V
-2.5 V
-5.25 V
-7.5 V
50%
150%
105%
R4
MAX CURRENT
motoring
clockwise
(motor)
generating
anticlockwise
(brake)
volts
current
setpoint
ramp
T13
T14
STOP
START
0 V
T3
speed setpoint
XIP T64
+24 V
RL2
RL2
START RELAY
OPTIONAL START (ramp to zero)