6.1
D
ISPLAY
E
RROR
C
ODES
Type of error
Description
ALARM
HIGH
OVER RANGE: this message is shown if PV is greater than URV by 10% of the
span.
ALARM
LOW
UNDER RANGE: this message is shown if PV is lower than LRV by 5% of the
span.
LCD OV
LCD OV: this message is shown if PV < -99999 or PV >99999.
EE CHK ERR
This message depends by an error configuration of the EEPROM memory
EE ADC ERR
This message is shown if there are PV calculus error in primary ADC input.
If it persist contact Spriano® for help
T EX AD ER
This message is shown if there are on external temperature signal calculus
error in secondary ADC input. If it persist contact Spriano® for help
PR ADC ER
This message is shown if there is an error in calculating the input of primary
ADC pressure signal. If persist contact Spriano® for help.
NaN
Indicates a sensor damage.