Manual for clima BSK4-F / clima BSK4-F230
LON fire damper actuator 4 ports
Order No.: 421 404 / 421 405
2.3. Installation
The binary inputs are only suitable for connections to potential-free
contacts. When laying the connecting cables, take any necessary
precautions. Laying distances to low-voltage circuits to maintain safe
isolation. The binary inputs fulfil Safety Extra Low Voltage (SELV)
requirements.
Connection of clima BSK4-F
The module clima BSK4-F provides a TP/FT-10 transceiver to connect to a free-
topology LON network. The module is supplied by 24V AC or DC. The module
power supply is identical to the motor supply. Please use the following
connection diagram:
BSK 1
BSK 2
+
+
-
-
-
-
-
-
24V AC/DC
LON A/B
to
p
bo
tto
m
M
to
p
bo
tto
m
M
BSK 3
BSK 4
to
p
bo
tto
m
M
to
p
bo
tto
m
M
L
O
N
E1.1 E1.2 E2.1 E2.2
A
B
A
B
E3.1 E3.2 E4.1 E4.2
M4
M4
M3
M3
M2
M1
M2
M1
<
-2
4V
If dampers with two end-position switches are used, connect them
to two adjacent binary inputs. For the „top (open)“-position is the
lower sub-number (e.g. E1.1) input to be used and the position
„bottom (close)“-position is to be connected to the higher sub-
number (e.g. E1.2).
Version 3.01
Page 12 / 39