6-4
Chapter 6: Testing Your Module
User’s Manual Pub. 0300181-07 Rev. A
Programming Software (APS) Reference Manual, Allen-Bradley publication
1746-6.11.
No Signal
After reviewing your configuration and LEDs for errors you may want to check
the input register Rate word for any indication of signal. If status bit 1 (Counter
Input State) is high and status bit 11 (Rate Zero) is high you may require a 1 to
10 k
Ω
pull-down resistor (depending on the in-put device) between your channel
input and channel common.
If you have an open collector output or a relay or contact type output you may
need the pull-down resistor. Refer to your sensor documentation for additional
information.
Verify that your input level thresholds are matched to your configuration word
input range.
Troubleshooting
Figure 6-2. Problem Resolution Flowchart
Continued on next page…
Continued from previous page…
Summary of Contents for SLC 500
Page 1: ...User s Manual Pub 0300181 07 Rev A ...
Page 8: ...viii SLC 500 50 kHz Counter Flowmeter Input Module User s Manual Pub 0300181 07 Rev A ...
Page 24: ...2 10 Chapter 2 Installation and Wiring User s Manual Pub 0300181 07 Rev A ...
Page 55: ...Chapter 6 Testing Your Module 6 5 User s Manual Pub 0300181 07 Rev A ...
Page 56: ...6 6 Chapter 6 Testing Your Module User s Manual Pub 0300181 07 Rev A ...
Page 60: ...7 4 Chapter 7 Maintaining your Module and Ensuring Safety User s Manual Pub 0300181 07 Rev A ...
Page 64: ...A 4 Appendix A Floating Point Rate Mode User s Manual Pub 0300181 07 Rev A ...