Multi IR Hydrocarbon and Hydrogen Flame Detector User Guide
54
Maintenance
4.1.2 Periodic Procedures
In addition to preventive cleaning and maintenance, the detector should be
functionally tested every 6 months or as dictated by local codes and
regulations. These tests should also be conducted if the detector has been
opened for any reason.
Power-Up Procedure
4.1.2.1
Perform the power-up procedure every time power is restored to the
system. Follow the instructions described in
on page 49.
Functional Test Procedure
4.1.2.2
Perform a functional test of the detector as described in
on page 30.
4.1.3 Keeping Maintenance Records
Maintenance operations performed on a detector should be recorded in a
logbook. The record should include the following:
Installation date
Contractor
Serial and tag number
Entries for every maintenance operation performed, including a
description of the operation, date, and personnel ID
If a unit is sent to SPECTREX or a distributor for service, a copy of the
maintenance records should accompany it.