Preparations for Installation
40
SafEye
TM
Open Path Detection System User Guide
5.2.4
The Source and Detector
The open path between the source and detector and the immediate
surroundings should be kept clear of obscuration that might hinder the
free movement of air in the protected area or block the infrared beam.
5.2.5
Guidance Tips for Gas Detector Locations
Guidance tips for gas detector locations in order to provide the best
detection coverage:
•
Below potential leak source for heavier than air gases.
•
Above potential leak sources for lighter than air gases.
•
Near to leak sources along the expected leak trajectory, taking into
account prevailing wind directions.
•
Between leak source and potential ignition sources.
5.3
Preparations for Installation
Upon receipt, verify the appropriate purchase order and record the P/N
and serial number of the source and detector units in the appropriate
logbook.
Carefully unpack the following equipment, observing any instructions
printed on or contained in the packaging list. Check the contents for any
possible damage caused from shipping and handling.
In the event of damage or loss in transit, notify the carrier and your
supplier immediately.
The Open Path set should include the following (in addition to this
manual):
•
Detector unit
•
Source unit
•
Two duct mounts
–
1 for the detector and 1 for the light source.
•
Telescope kit
•
Functional filters (to simulate warning and alarm level)
•
Magnetic mode selector
Commissioning kit 794247:
•
The commissioning kit includes magnetic mode selector, calibration
filters, and alignment tool. The kit is used during each SafEye
installation and then removed. The kit can be reused for all other
SafEye installations on the site. Therefore, only 1 set is provided for
several detectors.