Environmental Specifications
TM794200
Rev Ad, March 2019
37
Table 11: Detector/Source Weight and Dimensions
Detector/source
type and application
Al.
enclosure
Dimensions
Lb
Kg
Inch
mm
Detector for duct
mount
8.1
3.7
5.2x5.2x4.7 132x132x120
Detector for standard
mount
8.8
4.0
5.2x5.2x9
132x132x230
Source for duct mount
8.5
3.9
5.2x5.2x4.7 132x132x120
Source (reflector)
9.5
4.3
5.2x5.2x9
132x132x230
4.4
Environmental Specifications
The SafEye system is designed to withstand harsh environmental
conditions. The source and detector units compensate for adverse
conditions while maintaining accuracy:
•
High Temperature:
Designed to meet MIL-STD-810C, Method 501.1, Procedure II.
Operating temperature:
+185ºF/+85ºC
Storage temperature:
+185ºF/+85ºC
•
Low Temperature:
Designed to meet MIL-STD-810C, Method 502.1, Procedure I.
Operating temperature:
-40ºF/-40ºC
Storage temperature:
-40ºF/-40ºC
•
Humidity:
Designed to meet MIL-STD-810C, Method 507.1, Procedure IV.
Relative humidity of up to 95% for the operational temperature range.
•
Salt and Fog:
Designed to meet MIL-STD-810C, Method 509.1, Procedure I.
Exposure to a 5% salt solution for 48 hours.
•
Water and Dust
:
Designed to meet IP66 and IP67 per EN60529
Dust:
Totally protected against dust.