Output Signals
TM794200
Rev Ad, March 2019
25
Table 4: Standard (Default) 4
–
20mA Current for the Gas Channel
Current
Status and Description
0mA + 0.5mA
Fault 2 or low voltage
2mA ± 0.5mA
Fault 1
4mA ± 0.5mA
Zero reading - no gas detected
4
–
20mA
Continuous measuring of gas concentration at a range between
0 and 5 LEL*m or full scale
21mA
Concentration is over the range limit (more than full scale
concentration).
Table 5: Discrete Reading of 4
–
20mA at Different Detector Modes
Current Reading
Mode
LEL*m Setting
301
0 + 0.5mA
Fault 2 or low voltage
-
2 ± 0.5mA
Fault 1
-
4 ± 0.5mA
Standby
0
14 ± 0.5mA
Warning
1
19 ± 0.5mA
Alarm
1.5
3.7.2
Relays
The detector includes 3 relays:
•
Fault relay
•
Alarm relay
•
Accessory relay
Fault relay contacts are normally energized closed and opened when in
fault condition.
3.7.3
RS-485 Interface
The RS-485 input/output sends complete data information to a PC and
receives data or control commands from the PC. The protocol is Modbus-
compatible. Communication with the PC is operated through this interface
is executed only when used with appropriate host software.