AL-2 Installation, Maintenance & Operation Instructions

 

ALARM SYSTEM

 

 

DESCRIPTION 

 
Electrical alarm for use with emergency safety equipment.  Unit is supplied with an electric horn and flashing light 
that are activated by a vapor proof flow switch when connected to an emergency shower or eyewash. 

 
 

SPECIFICATIONS

 
FLOW SWITCH: ¾” Vapor Proof Flow Switch(Dwyer #V6EPSSS60). 
HORN: Edwards #876-N5 electric. 103dB @ 10 Ft. 
LIGHT: 40 Watt Bulb, 120V. 
SHIPPING WEIGHT: 21 lb. 

 

ELECTRICAL DATA:

 
 

ELECTRICAL SUPPLY: 120 VAC, 60 Cycle, Single Phase. 

 

ELECTRICAL RATING: 7.5 Amps @ 120 VAC. 

 

COMPLIANCE: Unit For Use In 

Non-Hazardous Locations

. Suitable for outdoor / wet  locations. 

 
*Power supply to be in compliance with (N.E.C.) 

National Electric Code.

 

 

 

OPTIONS 

 

 

◊ 

DPDT 

(Double Pole, Double Throw Flow Switch For Remote Locations)

 

◊ 

BLUE GLOBE 

◊ 

RED GLOBE 

◊ 

CLEAR GLOBE 

◊ 

BELL 

(97dB @ 10 Ft.)

 

 

 
 
 
 
 

 
INSTALLATION 

 

To avoid electric shock make sure power supply is shut off before doing any electrical maintenance to this unit.  
Power supply requirement is 120 VAC, 60 cycle, single phase. Ground-fault protection should be GFPD with a 
nominal 30 milliampere trip level to prevent nuisance tripping. Minimum 15 AMP breaker is required. Make sure 
power supply is in compliance with 

National Electric Code

 (N.E.C.). 

 
Use thread sealant on all joints. 
 
 

OPERATION 

 

 

 

Horn sounds and light flashes automatically when emergency equipment is activated and water flow triggers the 
flow switch.  Horn will sound and light will flash until emergency equipment is deactivated. 

 
 

TESTING PROGRAM 

 
The American National Standards Institute (ANSI) states that all safety emergency equipment shall be activated on 
a weekly basis to flush the line and verify proper operation. Speakman Company furnishes a testing record tag 
(91-0635) with each unit. On this tag the date of inspection and the inspectors initials should be noted.

 