Form 43343110
May 2021
-37-
14.0)
VENTING
This is a category lll appliance.
A.
BASIC FLUE VENTING
—
Venting must comply with the latest edition of the National Fuel Gas Code (ANSI
Z223.1-latest edition) or the authority having jurisdiction. Other venting references are in the equipment
volume of the ASHRAE Handbook.
Model
Heat
exchanger
length ft
Maximum vent length ft.
(4” diameter)
Maximum Fresh air
intake length ft (4”
diameter)
Max. combination of
fresh air and vent ft.
(4” diameter)
PCA-SS 75
20
45
50
75
PCA-SS 75
30
35
40
65
PCA-SS 100
30
45
50
75
PCA-SS 100
40
35
40
65
PCA-SS 125
30
60
50
75
PCA-SS 125
40
50
40
65
PCA-SS 125
50
40
30
55
PCA-SS 150
40
60
50
75
PCA-SS 150
50
50
40
65
Note:
1.
Vent lengths shown in the table are for horizontal and vertical venting. If a longer length of vertical or
horizontal venting is required contact the manufacturer for assistance with vent sizing.
2.
Vent cannot be used with the Cold air stopper accessory.
3.
Cold air stopper is only for use with fresh air intake assembly PN 44129500.
When installing a Defender series heater into a barn with stalls or partitions, we
recommend using a 40 ft. unit or shorter. This is due to the natural characteristic
of all tube heaters. Which is they have a significant temperature drop past 40 ft.
of tube.
Summary of Contents for PCA-SS 100
Page 13: ...Form 43343110 12 May 2021 7 1 DIMENSIONS STRAIGHT CONFIGURATION 48 HANGING CENTERS...
Page 14: ...Form 43343110 May 2021 13 7 2 HEATER ASSEMBLY JOINING OF TUBE SECTIONS...
Page 21: ...Form 43343110 20 May 2021...
Page 48: ...Form 43343110 May 2021 47 19 0 TROUBLESHOOTING GUIDE SINGLE STAGE N5 L5...
Page 49: ...Form 43343110 48 May 2021 TROUBLESHOOTING GUIDE SINGLE STAGE CONTINUED...
Page 50: ...Form 43343110 May 2021 49 TROUBLESHOOTING GUIDE SINGLE STAGE CONTINUED...
Page 51: ...Form 43343110 50 May 2021 19 1 TROUBLESHOOTING GUIDE TWO STAGE N7 L7...
Page 52: ...Form 43343110 May 2021 51 TROUBLESHOOTING GUIDE TWO STAGE CONTINUED...
Page 53: ...Form 43343110 52 May 2021 TROUBLESHOOTING GUIDE TWO STAGE CONTINUED...