Chapter 5 Function parameter
73
Ch
ap
ter 5
function input terminals of DI1 to DI10, DIx and DIy are for active pulse, DIn is for active level.
DIx
DIy
COM
SB2
DIn
Forward run
Three-wire operation
control
Reverse run
Digital common
terminals
SB1
SB3
Figure 5-5:Three-wire control mode 1
Of which:SB1: Stop button SB2: Forward button SB3: Reverse button
3: Three-wire control mode 2
In the mode, DIn is the enabled terminal, the running commands are given by DIx, the
direction is determined by the state of DIy.
The terminal function is set as follows:
Terminals
Set value
Description
DIx
1
Forward run (FWD)
DIy
2
Reverse run (REV)
DIn
3
Three-wire operation control
To run, firstly close DIn terminal, the motor run signal is generated by the ascendant edge of
DIx, the motor direction signal is generated by DIy status
To stop, you must disconnect DIn terminal signals Of which, DIx, DIy and DIn are the multi-
function input terminals of DI1 to DI10, DIx is for active pulse, DIy and DIn are for active level.
Command
FWD
REV
K
DIx
DIy
COM
SB2
DIn
Forward
Three-wire operation
Reverse
Digital common
SB1
K
Figure 5-6:Three-wire control mode 2
Of which: SB1: Stop button SB2: Run button
F1.11 Terminal UP / DOWN change rate
0.001Hz/s~65.535Hz/s
1.000Hz/s
☆
Used to set terminal UP/DOWN adjustment frequency, the rate of frequency change, i.e.
frequency change amount per second.
When F0.02 (frequency decimal point) is 2, the value range is 0.001Hz/s to 65.535Hz/s.
When F0.02 (frequency decimal point) is 1, the value range is 0.01Hz/s to 655.35Hz/s.
F1.12 Minimum input for AI Curve 1
0.00V to F1.14
0.30V
☆
F1.13 F1.12 corresponding setting
-100.0% to 100.0%
0.0%
☆
F1.14 Maximum input for AI Curve 1
F1.12 to 10.00V
10.00V
☆
F1.15 F1.14
corresponding setting
-100.0% to 100.0%
100.0%
☆
The above function codes are used to set the relationship between analog input voltage and its
representatives set value.
When the analog input voltage is more than the set Maximum Input (F1.14), the analog
voltage takes the Maximum Input as the calculated value, Similarly, when the analog input voltage
is less than the set Minimum Input (F1.12), according to the Setting Selection For AI Less Than
Minimum Input (F1.25), the analog voltage takes Minimal Input or 0.0% as the calculated value.
When the analog input is the current input, 1mA current is equivalent to 0.5V voltage.
AI1 input filter time is used to set AI1 software filter time, When the on-site analog quantity
is easily interfered, please increase the filter time to stabilize the detected analog quantity, but the
greater filter time, the slower analog detection response, the proper setting method depends on the