Chapter 5 Function parameter
42
Ch
ap
ter 5
226.
F7.21
Setting cumulative running
arrival time
0h to 36000h
0h
☆
227.
F7.22 Start protection selection
0: OFF 1: ON
0
☆
228.
F7.23
Frequency detection value
(FDT1)
0.00Hz to F0.19(maximum
frequency)
50.00Hz
☆
229.
F7.24
Frequency detection
hysteresis value (FDT1)
0.0% to 100.0% (FDT1 level)
5.0%
☆
230.
F7.25
Frequency reaches
detection width
0.00 to 100% (maximum frequency)
0.0%
☆
231.
F7.26
Frequency detection value
(FDT2)
0.00Hz to F0.19 (maximum frequency)
50.00Hz
☆
232.
F7.27
Frequency detection
hysteresis value (FDT2)
0.0% to 100.0% (FDT2 level)
5.0%
☆
233.
F7.28
Random arrivals
frequency detection value
1
0.00Hz to F0.19 (maximum
frequency)
50.00Hz
☆
234.
F7.29
Random arrivals
frequency detection width
1
0.00% to 100.0% (maximum
frequency)
0.0%
☆
235.
F7.30
Random arrivals
frequency detection value
2
0.00Hz to F0.19 (maximum
frequency)
50.00Hz
☆
236.
F7.31
Random arrivals
frequency detection width
2
0.00% to 100.0% (maximum
frequency)
0.0%
☆
237.
F7.32
Zero current detection
level
0.0% to 300.0% (rated motor current)
5.0%
☆
238.
F7.33
Zero current detection
delay time
0.01s to 360.00s
0.10s
☆
239.
F7.34
Overrun value of output
current
0.0% (not detected)
0.1% to 300.0% (rated motor current)
200.0%
☆
240.
F7.35
Output current overrun
detection delay time
0.00s to 360.00s
0.00s
☆
241.
F7.36 Random arrivals current 1 0.0% to 300.0% (rated motor current) -100.0%
☆
242.
F7.37
Random arrivals current 1
width
0.0% to 300.0% (rated motor current)
0.0%
☆
243.
F7.38 Random arrivals current 2 0.0% to 300.0% (rated motor current) -100.0%
☆
244.
F7.39
Random arrivals current 2
width
0.0% to 300.0% (rated motor current)
0.0%
☆
245.
F7.40
Module temperature
arrival
0℃ to 100℃
75℃
☆