Chapter 5 Function parameter
116
Ch
ap
ter 5
status will be low level. Between 3V~ 7V, hysteresis applies and keeps the last unambigious state.
E3.10 is to determine whether when the AI is used as DI, AI is made valid in high level state, or in
low level state. As for AI as DI feature set, same as the ordinary DI Settings, please refer to the F1
group setting instructions related DI. Below figure is AI input voltage taken as an example,
explains the relationship between input voltage of AI and the corresponding state of DI:
DC7V
Time(t)
AI input
voltage
ON
AI terminal state
DC3V
ON
OFF
Figure 5-35:
Judgment of effective state of AI
E3.11
VDO1 output
function
With the physical internal sub DIx
0
0
☆
See F2 group physical DO output option
1 to 40
E3.12
VDO2 output
function
With the physical internal sub DIx
0
0
☆
See F2 group physical DO output option
1 to 40
E3.13
VDO3 output
function
With the physical internal sub DIx
0
0
☆
See F2 group physical DO output option
1 to 40
E3.14
VDO4 output
function
With the physical internal sub DIx
0
0
☆
See F2 group physical DO output option
1 to 40
E3.15
VDO5 output
function
With the physical internal sub DIx
0
0
☆
See F2 group physical DO output option
1 to 40
E3.16
VDO output
effective
status
Units digit
VDO1
00000
☆
Positive logic
0
Negative logic
1
Tens digit
VDO2 (0 to 1, same as above)
Hundreds digit
VDO3 (0 to 1, same as above)
Thousands digit
VDO4 (0 to 1, same as above)
Ten thousands digit
VDO5 (0 to 1, same as above)
E3.17 VDO1 output delay time
0.0s to 3600.0s
0.0s
☆
E3.18 VDO2 output delay time
0.0s to 3600.0s
0.0s
☆
E3.19 VDO3 output delay time
0.0s to 3600.0s
0.0s
☆
E3.20 VDO4 output delay time
0.0s to 3600.0s
0.0s
☆
E3.21 VDO5 output delay time
0.0s to 3600.0s
0.0s
☆
VDO and DO output function is similar, can be used in conjunction with VDIx, to achieve
some simple logic control .
When VDOx output function is 0, output status is decided by DI1~DI5 input status on the
control board, VDOx and Dix one-to-one correspondence.
When the output function selection is not 0, VD0x function setting and using method is same
as D0 in F2 output parameter, please read F2 group parameter description.
The VDOx output valid status can be set by E3.16 setting, select positive logic or anti-logic.
5-2-19.
Motor parameters: b0.00-b0.35