5. ASSEMBLY 

Before mounting the unit, take into consideration the followings: 

 

accessibility/easy access for any servicing and maintenance works  

 

access to water and electrical installation  

 

possibility to mount the curtain directly at the gate entrance  

 

 It  is  advisable  to  mount  the  device  to  the  wall  or  the  ceiling  above  the  doorway  on  supporting  mount  pins  or  supporting 
constructions ( shapes and dimensions of the supporting construction may be individually designed in compliance with durability 
and strength requirements). 
 
Pay special attention to proper leveling of the device. If the device is not placed in a horizontal or vertical position, it may result 
in damaging the fan and consequently malfunctioning of the device. The air inlet and outlet must not be blocked by any objects. 
While  installing  the  unit,  remember  to  provide  easy  access  to  the  control  panel.    A  few  curtains  of  the  same  type  may  be 
installed in case of a bigger doorway. They must be assembled side-by-side to make an uninterrupted stream of air. The curtain 
is mounted horizontally or vertically for permanent (on the left/right side of the doorway). The GUARD PRO air curtain is advised 
to be wider (in case of horizontal mounting) or higher (in case of vertical mounting) than the gate way.  
 
If you decide on 

ACTIVE PROTECTION

 system, which is the assembly of curtains with water exchanger and without one, you 

have to mount air curtains with water exchangers on the bottom.  
 
When  connecting  the  curtain,  make  sure  that  maintenance  work  is  possible  to  be  conducted.  On  both  connection  nozzles 
manual shut-off valves should be installed in case of the necessity of disconnecting the unit. The hot water medium supply must 
be connected in accordance with the marking on the casing (inlet/outlet).   
When pipes being screwed to the heat exchanger make sure you secure the inlet connection of the heater to protect it against 
the torque (that may cause leakage in the heat exchanger). 
The  connections  of  heating  medium  with  the  threaded  nozzles  DIN  3/4”  should  be  based  on  the  project  carried  out  by  an 
authorized  designer.  In  case  of  connecting  the  curtain  to  the  heating  network  with  no  mixing  module,  a  water  filter  must  be 
installed. 

 

 

 
 
 
 
 
 

Connecting GUARDPRO curtains 
 

The  GUARDPRO

 

multi-purpose  connector

  is  designed  to  connect  curtains  and  to  mount  curtains  to  the  ceiling  (in  case  of 

horizontal mounting) or to the wall (in case of vertical mounting). 

The GUARDPRO multi-purpose connector

 is not included in 

the content of the delivery and is available optionally. The connector should be installed in accordance with the figures below. 
The required number of the GUARDPRO multi-purpose connectors may be calculated from the formula below 
 

 

 
 
Installation of connector inside the curtain                                    Installation of connector at the back of the 
 

                    

NOTICE ! 

   

!

 

Pay  special  attention  to  proper  leveling  of  the  device.  If  the  device  is  not  placed  horizontally  or  vertically,  it  may 

result  in damaging the fan and consequently the malfunction of the device. 

 

    

!

 

To sustain proper functioning of the device, keep safe distances as given in Figure below. 

 

Horizontal assembly

 (N – number of curtains) 

N x 4 = number of GUARDPRO multi-purpose connectors  
 

Vertical assembly

 (N -  number of curtains)  

(N x 4) – 2 = number of GUARDPRO multi-purpose connectors 
 

 

Summary of Contents for GUARDPR0 150E

Page 1: ... o Sp K ul Śląska 35 37 81 310 Gdynia Poland infolinia 801 055 155 tel 48 58 785 34 80 www sonniger com Sąd Rejonowy Gdańsk Północ VIII Wydział Gospodarczy Krajowego Rejestru Sądowego KRS 0000504509 NIP 586 227 35 14 Regon 22154369 kapitał zakładowy 1 655 000 PLN ...

Page 2: ... which is possible due to the airstream suitably directed that protects the entrance of cold air into a heated space In summers the curtains may be used as cooling devices preventing the entry of hot air from outside as well as air pollutants The GUARD PRO industrial air curtains are designed to protect against heat losses in the gateways of buildings of medium and high capacity especially such as...

Page 3: ...electric heaters Main advantages of PTC electric heaters No current on coil surface Lower temperaturę on coil surface in comparison to old type of electric heaters for ex electric wires long life solution Large space of PTC coil enhanced energy exchange between coil and air Fully automated regulation of heat capacity depending on air flow No risk of system overheat thanks to self colling option co...

Page 4: ...he power When the air curtain is connected directly to the cable please make sure there is a splitter protecting against any undesired disconnecting Pay special attention while transporting the device not to damage the casing When the device is being operated ensure the safety rules in accordance with the labor standards relating to the operation of any electrical devices Do not place any objects ...

Page 5: ...e that maintenance work is possible to be conducted On both connection nozzles manual shut off valves should be installed in case of the necessity of disconnecting the unit The hot water medium supply must be connected in accordance with the marking on the casing inlet outlet When pipes being screwed to the heat exchanger make sure you secure the inlet connection of the heater to protect it agains...

Page 6: ...t stop at the moment of opening gate Possibility to connect SPEEDER S2 speed regulator for two GUARD PRO curtains Possibility to connect SPEEDER S3 speed regulator for three GUARD PRO curtains Delivery does not include main maintenance switch To mount the curtain vertically make sure the air outlet of the curtain is as close as possible to the doorway and air gap is at the height of the upper edge...

Page 7: ...t be conducted in accordance with the applicable building regulations and standards The connection of the unit to the power supply must be conducted by a qualified specialist who is familiar with the Manual Fan s motor is equipped with internal thermal protection against overheating Power cable and a main switch are not included in the set Also the DOORSTOP door contact switch can be installed it ...

Page 8: ...RICAL SUPPLY OF CONTROL BOX POLARITY L N CONNECTION MUST BE KEPT AS PRESENTED ON ABOVE SCHEME L N CONNECTION CANNOT BE MIXED CONNECTED IN OPPOSITE WAY A dashed line indicates factory mounted jumpers that enables the operation of CONTROLBOX S3 without SPEEDER speed regulator When installing the SPEEDER controller jumpers must be taken out Required main priotection fuse C16 A Required electrical sup...

Page 9: ...er and techncial manual GUARDPRO are equipped with singe phase fans 1 230 V 50 Hz it is required to use additional protection for overload and shor circuit It is not allowed to start up GUARDPRO without grounded line 7 3 Connection scheme for GUARDPRO E electric heater with a switch and power board carried out by an installer NOTICE Supply of electrical heaters 3 x 400V 50 Hz GUARDPRO 150E supply ...

Page 10: ...ation and Maintenance Documentation of GUARD PRO air curtains v201708 www sonniger com 10 7 4 Connection scheme for GUARDPRO E electric heater with CONTROLBOX S3 and SPEEDER S2 or SPEEDER S3 speed regulator ...

Page 11: ...Operation and Maintenance Documentation of GUARD PRO air curtains v201708 www sonniger com 11 8 DIMENSIONS GUARD PRO 150W GUARD PRO 150C GUARD PRO 150E GUARD PRO 200W GUARD PRO 200C GUARD PRO 200E ...

Page 12: ...e goes below 0 C If the device is to operate in a room where the temperature goes below 0 C anti freeze liquid must be added to the water circulation system Anti freeze liquid must be appropriate for the material the exchanger is made of copper as well as other elements of the hydraulic system circulation The liquid must be diluted with water accordingly to the manufacturer s recommendation NOTICE...

Page 13: ...ystem but have not been delivered by the Seller and whose inappropriate functioning has a negative impact on the device s functioning Defects caused by connecting spare parts to the components that are not original parts Defects incurred by reselling of the product by the first buyer user to another buyer who dismantles installs the device that was previously installed and operated in a specific b...

Page 14: ...ice 6 The repair service including the replacement of the parts shall be done free of charge only if the representative of the installing contractor or the Service claims that the defect or malfunctioning of the device is caused by fault of the producer 7 Any and all costs cost of repair travel and exchanged components incurred due to the unjustified complaint especially in the situation when the ...

Page 15: ...l Serial number Date of purchase Start date Details of installation company Person activating the device Name of company Address Telephone Signature of a person who has started the device Installation works check ups inspections repairs Date The scope of installation works inspections repairs Signature and installation company stamp ...

Reviews: