Operation and Maintenance Documentation of GUARD PRO air curtains v201708

 

 

 www.sonniger.com 

4. GENERAL AND SAFETY PRINCIPLES

 

 

The GUARD PRO air curtains are manufactured in compliance with the rules and standards concerning quality, ecology, utility 
and work comfort . Before starting the device be sure to read the Manual carefully.  

The GUARD PRO air curtains are delivered ready-to-use in a cardboard package that is to protect from any mechanical 
damages. The package consists of: the device, the Manual (Operation and Maintenance Documentation) and the Guarantee. If 
the optional automatic control ordered, it shall be delivered in a separate package. Make sure all the aforementioned elements 
are in the package immediately after the delivery.  In the absence of any element, please fill in the suitable carrier document. 

NOTICE! 

 

Do not use the curtain in rooms containing any flammable and/or combustible substances, biological substances or in 
environments with corrosive air components. 

 

Do not use the curtain in rooms with relative humidity above 80% 

 

Do not leave the curtain ON unattended for longer periods  

 

Do not use the curtain without proper grounding 

 

Do not turn on the curtain with protective cover on 

 

Before conducting any maintenance or cleaning work or during  the break in operation  for an extended period of time, 
make sure you unplug the power cable 

 

To connect the air curtain, use a supply cable with a fork that protects against unintended disconnecting from the 
power 

 

When the air curtain is connected directly to the cable, please make sure there is a splitter protecting against any 
undesired disconnecting  

 

Pay special attention while transporting the device not to damage the casing 

 

When the device is being operated, ensure the safety rules in accordance with the labor standards relating to the 
operation of any electrical devices  

 

Do not place any objects on the curtain or reduce the airflow in order to ensure the fire safety and if sparks or a 
damaged supply cable noticed, discontinue the operation immediately 

 

Electricity network, to which the curtain is connected, should be protected against overloading and short circuit 

 

CAUTION! 

 

 

For reasons of serious danger to electric shock any exchanges of supply cable must be performed by a qualified 
specialist 

 

For reasons of serious danger to electric shock disconnect the power supply prior to conducting any repair or 
maintenance work 

 

Any leakage repairs of the heating medium in the device, of which pipes are under pressure, is strictly prohibited 

 

Cut-off/stop valve must be used to supply a heating medium 

 

It is prohibited to connect grounding-type plug to water pipe, gas tubes, lightning conductors, telephone or antenna 
network 

 

Wait for at least 3 hours before connecting the device to the supply power if the temperature while transporting is 
below zero 

 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 

NOTICE ! 

!

 

Before mounting the device,  read the manual carefully and adhere to the rules concerning the mounting 
procedures. Not applying to the rules may result in the inappropriate functioning of the device and the loss of the 
guarantee rights. 
 

!

 

Pay special attention when working with electrical elements of the device. 

 

Summary of Contents for GUARDPR0 150E

Page 1: ... o Sp K ul Śląska 35 37 81 310 Gdynia Poland infolinia 801 055 155 tel 48 58 785 34 80 www sonniger com Sąd Rejonowy Gdańsk Północ VIII Wydział Gospodarczy Krajowego Rejestru Sądowego KRS 0000504509 NIP 586 227 35 14 Regon 22154369 kapitał zakładowy 1 655 000 PLN ...

Page 2: ... which is possible due to the airstream suitably directed that protects the entrance of cold air into a heated space In summers the curtains may be used as cooling devices preventing the entry of hot air from outside as well as air pollutants The GUARD PRO industrial air curtains are designed to protect against heat losses in the gateways of buildings of medium and high capacity especially such as...

Page 3: ...electric heaters Main advantages of PTC electric heaters No current on coil surface Lower temperaturę on coil surface in comparison to old type of electric heaters for ex electric wires long life solution Large space of PTC coil enhanced energy exchange between coil and air Fully automated regulation of heat capacity depending on air flow No risk of system overheat thanks to self colling option co...

Page 4: ...he power When the air curtain is connected directly to the cable please make sure there is a splitter protecting against any undesired disconnecting Pay special attention while transporting the device not to damage the casing When the device is being operated ensure the safety rules in accordance with the labor standards relating to the operation of any electrical devices Do not place any objects ...

Page 5: ...e that maintenance work is possible to be conducted On both connection nozzles manual shut off valves should be installed in case of the necessity of disconnecting the unit The hot water medium supply must be connected in accordance with the marking on the casing inlet outlet When pipes being screwed to the heat exchanger make sure you secure the inlet connection of the heater to protect it agains...

Page 6: ...t stop at the moment of opening gate Possibility to connect SPEEDER S2 speed regulator for two GUARD PRO curtains Possibility to connect SPEEDER S3 speed regulator for three GUARD PRO curtains Delivery does not include main maintenance switch To mount the curtain vertically make sure the air outlet of the curtain is as close as possible to the doorway and air gap is at the height of the upper edge...

Page 7: ...t be conducted in accordance with the applicable building regulations and standards The connection of the unit to the power supply must be conducted by a qualified specialist who is familiar with the Manual Fan s motor is equipped with internal thermal protection against overheating Power cable and a main switch are not included in the set Also the DOORSTOP door contact switch can be installed it ...

Page 8: ...RICAL SUPPLY OF CONTROL BOX POLARITY L N CONNECTION MUST BE KEPT AS PRESENTED ON ABOVE SCHEME L N CONNECTION CANNOT BE MIXED CONNECTED IN OPPOSITE WAY A dashed line indicates factory mounted jumpers that enables the operation of CONTROLBOX S3 without SPEEDER speed regulator When installing the SPEEDER controller jumpers must be taken out Required main priotection fuse C16 A Required electrical sup...

Page 9: ...er and techncial manual GUARDPRO are equipped with singe phase fans 1 230 V 50 Hz it is required to use additional protection for overload and shor circuit It is not allowed to start up GUARDPRO without grounded line 7 3 Connection scheme for GUARDPRO E electric heater with a switch and power board carried out by an installer NOTICE Supply of electrical heaters 3 x 400V 50 Hz GUARDPRO 150E supply ...

Page 10: ...ation and Maintenance Documentation of GUARD PRO air curtains v201708 www sonniger com 10 7 4 Connection scheme for GUARDPRO E electric heater with CONTROLBOX S3 and SPEEDER S2 or SPEEDER S3 speed regulator ...

Page 11: ...Operation and Maintenance Documentation of GUARD PRO air curtains v201708 www sonniger com 11 8 DIMENSIONS GUARD PRO 150W GUARD PRO 150C GUARD PRO 150E GUARD PRO 200W GUARD PRO 200C GUARD PRO 200E ...

Page 12: ...e goes below 0 C If the device is to operate in a room where the temperature goes below 0 C anti freeze liquid must be added to the water circulation system Anti freeze liquid must be appropriate for the material the exchanger is made of copper as well as other elements of the hydraulic system circulation The liquid must be diluted with water accordingly to the manufacturer s recommendation NOTICE...

Page 13: ...ystem but have not been delivered by the Seller and whose inappropriate functioning has a negative impact on the device s functioning Defects caused by connecting spare parts to the components that are not original parts Defects incurred by reselling of the product by the first buyer user to another buyer who dismantles installs the device that was previously installed and operated in a specific b...

Page 14: ...ice 6 The repair service including the replacement of the parts shall be done free of charge only if the representative of the installing contractor or the Service claims that the defect or malfunctioning of the device is caused by fault of the producer 7 Any and all costs cost of repair travel and exchanged components incurred due to the unjustified complaint especially in the situation when the ...

Page 15: ...l Serial number Date of purchase Start date Details of installation company Person activating the device Name of company Address Telephone Signature of a person who has started the device Installation works check ups inspections repairs Date The scope of installation works inspections repairs Signature and installation company stamp ...

Reviews: