Technical data | 15
KD-557 | 1000241 | EN | 02
91 / 100
15.2 sonnenProtect 4000 (optional)
System data (AC)
sonnenProtect 4000
Nominal power
4,000 W
Nominal frequency
50 Hz
Output voltage
230/240 V
Overload (30 min.)
max. 4,600 W
Power factor range
0 capacitive ... 0 inductive
Max. output current (duration/100 ms)
20 A / 23 A
Short-circuit current
40 A
Network configuration in emergency op-
eration
TN
Mains connection
single-phase, L / N / PE
Mains connection fuse
Miniature circuit breaker | Type B | 20 A
Operating concept
Single-phase power supply via emergency circuit(s). The
switch to emergency operation takes place automatic-
ally through the storage system.
Switchover time
approx. 15 seconds
Threshold power
none (starting from 0 W)
Dimensions/weight
Dimension (H/W/D) in cm
52/23/12
Weight in kg
approx. 10
Safety/protective
devices
Protection class
II
Degree of Protection
IP65
Overvoltage category
2
Required fault current monitoring
Residual current device (RCD) with a rated differential
current of 300 mA; requirements on site must be ob-
served.
Ambient conditions
Environment
Indoor/Outdoor
Pollution degree
3
Operating temperature range
-5 °C ... 50 °C
Max. rel. humidity
100%, condensing
Permissible installation altitude
2,000 m above sea level
Additional ambient conditions
The ambient conditions prescribed for the
storage system apply.