List of registers
Name of the variable
1
float
LO Flow m3/h
2
HI
3
long int
HI Positive volume m3
4
LO
5
int
Positive volume l
6
float
LO Liquid speed m/s
7
HI
8
bit
errors 1... 16
9
long int
HI
10
LO
11
long int
HI Working time s
12
LO
13
long int
HI Time of correct work s
14
LO
15
long int
HI Temporary volume liter
16
LO
17
float
LO Temporary volume
18
HI measurement time s
19
int
20
float
LO 5 min average of the flow
21
HI
22
float
LO Hour average of the flow m3
23
HI
24
int
CRCL
25
Reserved
26
Reserved
27
char
work mode: desired, current
28
int
CRC
29
int
Register
no
Variable
type
Flowmeter serial number
program vesion
AB probes adj., aut./manual
Remarks:
16 bit registers, char, int, long int – variable without a sign
CRCL – checksum saved afer verification
CRC – current checksum calculated every 60s
Register no 8 (errors), 1 in a given position means:
15 – correct measurement
14 – EF path signal adjustment
13 – CD path signal adjustment
12 – AB path signal adjustment
11 – low signal from EF pair of probes
10 – reserved
9 – low signal from the CD pair of probes
8 – outside the range of acceptable liquid speed
7 – checksum or mode of work inconsistency
6 – the flow exceeds the programmed current range value
5 – the same as bit 1
4 – reserved
3 – reserved
2 – flowmeter self test
1 – lack of liquid in the pipeline, damaged probe cables, damage of the
analogue part of the flowmeter, liquid aeration, electrical interferences
0 – low signal from the AB pair of probes